Date Code 20011205
Inputs, Outputs, Timers, and Other Control Logic
7-23
SEL-311B Instruction Manual
Table
7.5: SEL
OGIC
Control Equation Settings for Switching Active Setting Group
Between Setting Groups 1 and 4
Setting Group 1
Setting Group 4
SV8 = SG1
SV8 = SG4
SS1 = 0
SS1 = IN105 * SV8T
SS2 = 0
SS2 = 0
SS3 = 0
SS3 = 0
SS4 = IN105 * SV8T
SS4 = 0
SS5 = 0
SS5 = 0
SS6 = 0
SS6 = 0
SEL
OGIC
control equation timer input setting SV8 in Table
7.5 has logic output SV8T, shown in
7.19 for both setting Groups 1 and 4.
Figure
7.19: SEL
OGIC
Control Equation Variable Timer SV8T Used in Setting Group
Switching
In this example, timer SV8T is used in both setting groups—different timers could have been
used with the same operational result. The timers reset during the setting group change, allowing
the same timer to be used in both setting groups.
Timer pickup setting SV8PU is set greater than the pulse width of the SCADA contact (Figure
7.18). This allows only one active setting group change (e.g., from setting Group 1 to 4) for each
pulse of the SCADA contact (and subsequent assertion of input IN105). The functions of the
SEL
OGIC
control equations in Table
7.5 are explained in the following example.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......