4-36
Operation Within SEL-2030
Date Code 20010105
SEL-2711 Instruction Manual
Relative
Address
Description
Units
Range
69
Unused, always 8000h
70
Phase A peak demand current (IA)
amps, primary
0-32767 A
71
Phase B peak demand current (IB)
amps, primary
0-32767 A
72
Phase C peak demand current (IC)
amps, primary
0-32767 A
73
Residual peak demand current (IR)
amps, primary
0-32767 A
74
Power peak demand, whole part (P)
MW, primary
-32767-32767 MW
75
Power peak demand, fractional part (P)
MW/10000, primary
-0.9999-0.9999 MW
76
Reactive power peak demand, whole part (Q)
MVAR, primary
-32767-32767 MVAR
77
Reactive power peak demand, fractional part (Q)
MVAR/10000, primary
-0.9999-0.9999 MVAR
78
Negative-sequence peak demand current (3I2)
amps, primary
0-32767 A
79
Unused, always 8000h
80
Month of last meter data acquisition
months
1-12
81
Day of last meter data acquisition
days
1-31
82
Year of last meter data acquisition
years
1900-2100
83
Hour of last meter data acquisition
hours
0-23
84
Minute of last meter data acquisition
minutes
0-59
85
Second of last meter data acquisition
seconds
0-59
86-159
Reserved - always 8000h
160
Relay word rows 0 and 1
161
Relay word rows 2 and 3
162
Relay word rows 4 and 5
163
Relay word rows 6 and 7
164
Relay word row 8 with LSB always 0
165-209
Reserved - always 8000h
210
Month of most recent event
months
1-12
211
Day of month of most recent event
days
1-31
212
Year of most recent event
years
1900-2100
213
Hour of most recent event
hours
0-23
214
Minute of most recent event
minutes
0-59
215
Second of most recent event
seconds
0-59
216
Millisecond of most recent event
milliseconds
0-999
217-219
Unused - always 8000h
220
Event type
TBD
TBD
221
Shot
222
Fault location, whole part
-32767-32767
223
Fault location, fractional part
-0.9999-0.9999
224
Fault targets of most recent fault
TBD
225-233
Unused - always 8000h
234
Fault current of most recent fault
amps, primary
0-32767 A
235
Fault current of most recent fault, fractional
part, always 0
amps, primary
0
236-239
Unused - always 8000h
240-259
Reserved - always 8000h
260
1
st
event month
months
1-12
261
1
st
event day of month
days
1-31
262
1
st
event year
years
1900-2100
263
1
st
event hour
hours
0-23
264
1
st
event minute
minutes
0-59
265
1
st
event second
seconds
0-59
266
1
st
event millisecond
milliseconds
0-999
267
1
st
event type
TBD
268
1
st
event fault location, whole part
-32767-32767
269
1
st
event fault location, fractional part
-0.9999-0.9999
270-271
Unused - always 8000h
272
1
st
event group number
1-6
273
1
st
event targets
TBD
274-275
Unused - always 8000h
276
1
st
event fault current, whole part
amps, primary
0-32767 A
277
1
st
event fault current, fractional part, always 0
amps, primary
0
278-279
Unused - always 8000h
280
2
nd
event month
months
1-12
.
.
.
.
.
.
.
.
.
.
.
.
497
12
th
event fault current, fractional part, always 0
amps, primary
0
498-499
Unused - always 8000h