4
© 2013–2018 by Schweitzer Engineering Laboratories, Inc. All rights reserved.
All brand or product names appearing in this document are the trademark or registered
trademark of their respective holders. No SEL trademarks may be used without written
permission. SEL products appearing in this document may be covered by U.S. and Foreign
patents.
Schweitzer Engineering Laboratories, Inc. reserves all rights and benefits afforded under
federal and international copyright and patent laws in its products, including without lim-
itation software, firmware, and documentation.
The information in this document is provided for informational use only and is subject to
change without notice. Schweitzer Engineering Laboratories, Inc. has approved only the
English language document.
This product is covered by the standard SEL 10-year warranty. For warranty details, visit
selinc.com or contact your customer service representative.
*PDS2245-04*
2350 NE Hopkins Court • Pullman, WA 99163-5603 U.S.A.
Tel: +1.509.332.1890 • Fax: +1.509.332.7990
selinc.com • [email protected]
SEL-2245-4 Data Sheet
Date Code 20180629
Record Pretrigger:
0.05 s minimum to a maximum of
(record length –0.05) s
Waveform File Format:
COMTRADE (IEEE C37.111-1999
compliant)
Type Tests
Environmental Tests
Enclosure Protection:
IEC 60529:2001 + CRGD:2003
IP3X excluding the terminal blocks
Vibration Resistance:
IEC 60255-21-1:1988
Vibration Endurance, Severity: Class 2
Vibration Response, Severity: Class 2
Shock Resistance:
IEC 60255-21-2:1988
Bump Test, Severity: Class 1
Shock Withstand, Severity: Class 1
Shock Response, Severity: Class 2
Seismic:
IEC 60255-21-3:1993
Quake Response, Severity: Class 2
Cold:
IEC 60068-2-1:2007
–40°C, 16 hours
Dry Heat:
IEC 60068-2-2:2007
+85°C, 16 hours
Damp Heat, Cyclic:
IEC 60068-2-30:2005
25°C to 55°C, 6 cycles,
95% relative humidity
Dielectric Strength and Impulse Tests
Impulse:
IIEC 60255-5:2000
IEEE C37.90-2005
Severity Level:
0.5 Joule, 5 kV CT/PT inputs
Dielectric (HiPot):
IEC 60255-5:2000
IEEE C37.90-2005
Severity Level:
2500 Vac CT/PT inputs for 1 minute
RFI and Interference Tests
EMC Immunity
Electrostatic Discharge
Immunity:
IEEE C37.90.3-2001
IEC 60255-22-2:2008
IEC 61000-4-2:2008
Severity Level: 8 kV contact discharge
15 kV air discharge
Radiated RF Immunity:
IEEE C37.90.2-2004
Severity Level: 35 V/m
IEC 61000-4-3:2008
IEC 60255-22-3:2007
Severity Level: 10 V/m
Digital Radio Telephone
RF Immunity:
ENV 50204:1995
Severity Level:
10 V/m at 900 MHz and 1.89 GHz
Conducted RF Immunity: IEC 60255-22-6:2001
IEC 61000-4-6:2008
Severity Level: 10 Vrms
Surge Immunity:
IEC 60255-22-5:2008
IEC 61000-4-5:2005
Severity Level: 1 kV Line to Line,
2 kV Line to Earth
(202 ms filter on RMS voltages and
frequencies, 33 ms filter on fundamental
frequencies)
Fast Transient, Burst
Immunity:
IEC 60255-22-4:2008
IEC 61000-4-4:2011
Severity Level: Class A: 4 kV, 5 kHz;
2 kV, 5 kHz on communications ports
Magnetic Field
Immunity:
IEC 61000-4-8:2009
Severity Level: 1000 A/m for 3 seconds,
100 A/m for 1 minute
IEC 61000-4-9:2001
Severity Level: 1000 A/m
IEC 61000-4-10:2001
Severity Level: 100 A/m
Surge Withstand
Capability Immunity:
IEC 60255-22-1:2007
Severity Level: 2.5 kV common-mode
1.0 kV differential-mode
IEEE C37.90.1-2002
Severity Level: 2.5 kV Oscillatory
4.0 kV Fast Transient
Oscillatory Waves
Immunity:
IEC 61000-4-12:2006
Severity Level: Ring Wave: 2 kV
common, 1.0 kV differential
Oscillatory: 2.5 kV common,
1.0 kV differential
Common Mode
Disturbance Immunity:
IEC 61000-4-16:2002
Frequency: 0 Hz to 150 Hz
Severity Level: Level 4, Segment 4:
30 Vrms open-circuit, 15 kHz–150 kHz
Emissions
Radiated and Conducted
Emissions:
IEC 60255-25:2000
Severity Level: Class A