background image

4

© 2013–2018 by Schweitzer Engineering Laboratories, Inc. All rights reserved.

All brand or product names appearing in this document are the trademark or registered
trademark of their respective holders. No SEL trademarks may be used without written
permission. SEL products appearing in this document may be covered by U.S. and Foreign
patents.

Schweitzer Engineering Laboratories, Inc. reserves all rights and benefits afforded under
federal and international copyright and patent laws in its products, including without lim-
itation software, firmware, and documentation.

The information in this document is provided for informational use only and is subject to
change without notice. Schweitzer Engineering Laboratories, Inc. has approved only the
English language document.

This product is covered by the standard SEL 10-year warranty. For warranty details, visit
selinc.com or contact your customer service representative.

*PDS2245-04*

2350 NE Hopkins Court • Pullman, WA 99163-5603 U.S.A.

Tel: +1.509.332.1890 • Fax: +1.509.332.7990

selinc.com • [email protected]

SEL-2245-4 Data Sheet

Date Code 20180629

Record Pretrigger:

0.05 s minimum to a maximum of 

(record length –0.05) s

Waveform File Format:

COMTRADE (IEEE C37.111-1999 

compliant)

Type Tests

Environmental Tests

Enclosure Protection:

IEC 60529:2001 + CRGD:2003
IP3X excluding the terminal blocks

Vibration Resistance:

IEC 60255-21-1:1988

Vibration Endurance, Severity: Class 2
Vibration Response, Severity: Class 2

Shock Resistance:

IEC 60255-21-2:1988

Bump Test, Severity: Class 1
Shock Withstand, Severity: Class 1
Shock Response, Severity: Class 2

Seismic:

IEC 60255-21-3:1993

Quake Response, Severity: Class 2

Cold:

IEC 60068-2-1:2007

–40°C, 16 hours

Dry Heat:

IEC 60068-2-2:2007

+85°C, 16 hours

Damp Heat, Cyclic:

IEC 60068-2-30:2005

25°C to 55°C, 6 cycles,
95% relative humidity

Dielectric Strength and Impulse Tests

Impulse:

IIEC 60255-5:2000 
IEEE C37.90-2005 

Severity Level:

0.5 Joule, 5 kV CT/PT inputs

Dielectric (HiPot):

IEC 60255-5:2000 
IEEE C37.90-2005

Severity Level:

2500 Vac CT/PT inputs for 1 minute

RFI and Interference Tests

EMC Immunity

Electrostatic Discharge 

Immunity:

IEEE C37.90.3-2001
IEC 60255-22-2:2008 
IEC 61000-4-2:2008 

Severity Level: 8 kV contact discharge
15 kV air discharge

Radiated RF Immunity:

IEEE C37.90.2-2004 

Severity Level: 35 V/m

IEC 61000-4-3:2008
IEC 60255-22-3:2007

Severity Level: 10 V/m

Digital Radio Telephone 

RF Immunity:

ENV 50204:1995 

Severity Level: 

10 V/m at 900 MHz and 1.89 GHz

Conducted RF Immunity: IEC 60255-22-6:2001

IEC 61000-4-6:2008

Severity Level: 10 Vrms

Surge Immunity:

IEC 60255-22-5:2008
IEC 61000-4-5:2005

Severity Level: 1 kV Line to Line, 
2 kV Line to Earth
(202 ms filter on RMS voltages and 
frequencies, 33 ms filter on fundamental 
frequencies)

Fast Transient, Burst 

Immunity:

IEC 60255-22-4:2008
IEC 61000-4-4:2011

Severity Level: Class A: 4 kV, 5 kHz;
2 kV, 5 kHz on communications ports

Magnetic Field 

Immunity:

IEC 61000-4-8:2009 

Severity Level: 1000 A/m for 3 seconds, 
100 A/m for 1 minute

IEC 61000-4-9:2001
   Severity Level: 1000 A/m
IEC 61000-4-10:2001
   Severity Level: 100 A/m

Surge Withstand 

Capability Immunity:

IEC 60255-22-1:2007 

Severity Level: 2.5 kV common-mode 
1.0 kV differential-mode 

IEEE C37.90.1-2002

Severity Level: 2.5 kV Oscillatory
4.0 kV Fast Transient 

Oscillatory Waves 

Immunity:

IEC 61000-4-12:2006

Severity Level: Ring Wave: 2 kV 
common, 1.0 kV differential 
Oscillatory: 2.5 kV common, 
1.0 kV differential

Common Mode 

Disturbance Immunity:

IEC 61000-4-16:2002

Frequency: 0 Hz to 150 Hz 
Severity Level: Level 4, Segment 4: 
30 Vrms open-circuit, 15 kHz–150 kHz

Emissions

Radiated and Conducted 

Emissions:

IEC 60255-25:2000 

Severity Level: Class A