2.
Set a contact to close upon assertion of the 59S bit. Connect that contact to
start an external timer.
3.
Set a second contact to close upon assertion of the VSC bit. Connect that
contact to stop the external timer.
4.
Connect a voltage source to the synch-check voltage input. Apply voltage
above the 59VHI setting. When the 59S bit asserts, the external timer should
start. When the voltage conditions of hot synch/dead pol. have been valid for
VCT time, the VSC bit should assert, stopping the external timer. Verify that
the timer reading is equal to the VCT timer setting. If PSVC = E, continue
with Step 5.
5.
Set a contact to close upon assertion of the 59P bit. Connect that contact to
start an external timer.
6.
Set a second contact to close upon assertion of the VSC bit. Connect that
contact to stop the external timer.
7.
Connect a three-phase voltage source to the polarizing voltage inputs. Apply
voltage above the 59VHI setting. When the 59P bit asserts, the external timer
should start. When the voltage conditions of hot pol/dead synch have been
valid for VCT time, the VSC bit should assert, stopping the external timer.
Verify that the timer reading is equal to the VCT timer setting.
SYNCHRONISM CHECKING LOGIC TESTS
Purpose:
Method: 1.
2.
3.
4.
Verify operation of the relay synchronism checking function.
Using the SHOWSET command, check the relay SYNCP, 25T, and 25DV
settings.
Set a contact to close upon assertion of the 59P bit.
Connect a voltage source to the polarizing voltage input selected in the SYNCP
setting. Connect a second voltage source to the voltage input which lags the
input selected by the SYNCP setting. Figure 7.12 shows voltage connections
when SYNCP = A. Apply voltage to the first voltage input above the 59VHI
setting. Adjust the phase angle of the second voltage source to lag the first by
120°. Increase the second voltage input until the 59P bit asserts.
Set a contact to close upon assertion of the 59S bit. Connect that contact to
start an external timer.
Date Code 920508
Maintenance & Testing
SEL-221F, -1 Instruction Manual
7-39
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...