LOSS-OF-POTENTIAL TEST
Purpose:
Verify the SET LOP and CLEAR LOP conditions. The following equations
show the SET LOP and CLEAR LOP logic equations.
SET LOP = 47QL * NOT(46 QL)
+ NOT(47P) * NOT (50P)
CLEAR LOP = NOT(47QL) * 47P
Where: 47 QL = 14 V of V2
46QL = 0.083 A of I2
47P = 14 V of V1
50P = Current in any phase over the 50P setting
Method: Table 7.13 provides the voltage and current sets required to create SET LOP and
CLEAR LOP conditions.
Table 7.12: Conditions To Test the SET LOP and CLEAR LOP Logic
SET LOP:
VA
VB
V C
IA
I B
IC
0.00
67.00
67.00
0.00
0.00
0.00
Volts/Amps
0.0° -120.0°
120.0°
0.0°
0.0°
0.0°
Degrees
CLEAR LOP:
VA
VB
VC
IA
IB
IC
67.00
67.00
67.00
0.00
0.00
0.00
Volts/Amps
0.0° -120.0°
120.0°
0.0°
0.0°
0.0°
Degrees
Note:
The relay may use LOP detection in a number of different ways. Check
your LOPE setting and consult the SPECIFICATIONS section to determine
how the relay is set to use LOP detection.
7-32
Maintenance & Testing
SEL-221F, -1 Instruction Manual
Date Code 920508
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...