“Job Done” Examples - (Example 8)
Date Code 20010518
SEL-2020 Instruction Manual
D
EFINING THE
S
OLUTION
Set the SEL-2020
1. Use SET P 12 to configure Port 12 as an “Other IED” port with the DGH 1000
communication parameters. Use the SET A 12 command to make the following settings:
•
Set AUTOBUF=N so Port 12 does not store unsolicited messages.
•
Define message trigger ISSUE1 to send a message every 30 seconds.
•
Create a message, $1RD\00D, that is sent to the DGH 1000 when triggered.
•
Set PARSE and NUM to accept one floating-point number.
Test the Operation
1. Use the TOGGLE command to force data collection and the VIEW command to view the
collected data.