The baud rate for each port is set by jumpers near the front of the main board. You can
access these jumpers by removing either the top cover or front panel. Available baud rates
are 300, 600, 1200, 2400, 4800, or 9600.
Caution:
Do not select two baud rates for the same port as this can damage the relay
baud rate generator. The relay is shipped with PORT 1 set to 300 baud and
PORT 2 set to 2400 baud.
The serial data format is:
Eight data bits
Two stop bits
No parity
This format may not be changed. The serial communications protocol appears in Section 4.
The SEL-167D relay does not include a front panel serial data interface.
Input Power
Terminals marked + and - should be connected to a source of control voltage. Polarity of dc
power is unimportant. Power requirement is about 12 watts. Terminal marked GND should
be wired to the relay rack ground reference for grounding the instrument frame.
Contact Inputs
Six input circuits are provided. They are listed below.
Direct Trip
Direct Close
Permissive Trip
52A Monitor
Block Trip
External Trigger
To assert an input, nominal control voltage is applied to the appropriate terminal pair.
Polarity is unimportant. The following table shows input parameters.
Table 2.2: Input Parameters
Logic Input Rating
Contact Input Range
24 Vdc
10 - 30 Vdc
48 Vdc
25 - 60 Vdc
125 Vdc
60 - 200 Vdc
250 Vdc
200 - 280 Vdc
Date Code 920326
Specifications
SEL-267D/167D Instruction Manual
2-7
Summary of Contents for SEL-167D
Page 3: ......
Page 6: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Page 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Page 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Page 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Page 88: ...SAMPLE EVENT REPORT ...
Page 114: ......
Page 115: ......