Parameter IC 4000/1 and setting
The burner control unit IC 4000/1 is already factory
preset.
The parameters can be read out by the Schwank
Service Software IC 4000 [RS-485 interface board]
and if necessary to be changed.
Parameter selection and settings can made
manually direct at IC 4000/1 by the two push
buttons SW 2 and SW 3 and the 7-segment display.
For this, unscrew the lid of the IC 4000/1 burner
control.
After power supply IC 4000/1 following sequence is
shown on the 7-segment display:
1. segment test, all 7 segments light up
2. software version [two successive numbers]
3. burner control software: 1
Parameter Parameter name and
parameter value definitions
Factory
setting
Set
range
PP01
Setting Communication
0: No MODBUS control [e.g. ThermoControl M+]
1: MODBUS contol by SchwankControl Touch
1
0 - 1
PP02
Drive Fan
0: Phase angle control driven
1: PWM driven
1
0 -1
PP03
[Note 1]
Value phase angle control fan
0 – 80
@ power supply 230V:
value „0” = 153 V, value „80“ = 230 V
according to
type
see Tab. 5,
page 22
0 - 80
PP07
[Note 1]
minimal modulation current
40 mA – “PP08 max modulation current – 5 mA”
[Note 2]
according to
type
see Tab. 5,
page 22
40 - 160
PP08
[Note 1]
maximal modulation current
“PP07 min modulation c 5 mA” – 165 mA
[Note 2]
according to
type
see Tab. 5,
page 22
45 - 165
Note 1
: Parameter PP03, 07 and 08 only relevant for modulating operation lambdaPlus
Note 2
: PP08 MAX MODULATION CURRENT > = [PP07 MIN MODULATION C 5]
Tab 8: Parameter level IC 4000/1