![schmersal TESK Series Operating Instructions Manual Download Page 3](http://html.mh-extra.com/html/schmersal/tesk-series/tesk-series_operating-instructions-manual_1213503003.webp)
3
TESK
Operating instructions
Hinge safety switch
EN
Utilisation category:
AC-15, DC-13
Rated operating current/voltage I
e
/U
e
:
-with cable:
2 A / 230 VAC
1 A / 24 VDC
-with connector plug M12:
1 A / 24 VDC
Rated insulation voltage U
i
:
- with cable:
300 V
- with connector plug, M12 8-pin:
30 V (PELV to DIN EN 60204-1)
- with connector plug, M12 5-pin:
60 V
Rated impulse withstand voltage U
imp
:
- with cable:
2.5 kV
- with connector plug, M12 8-pin:
0.5 kV
- with connector plug, M12 5-pin:
0.8 kV
Thermal test current I
the
:
2.5 A
Rated operating voltage U
e
max:
- with cable:
230 V
- with connector plug M12, 8-pin:
30 V
- with connector plug M12, 5-pin:
60 V
Max. fuse rating:
2 A gG D-fuse
Switching of low voltages:
1 mA / 3 VDC
Mechanical breaking load (see fig. 1):
- F1:
5,000 N
- F2:
5,000 N
See Section 7.3 Load details
F1
F2
F1
F2
Fig. 1
C
For use in NFPA 79 Applications only.
2.5 Safety classification
Standards:
ISO 13849-1
Envisaged structure:
- Basically:
applicable up to Cat. 1 / PL c
- With 2-channel usage and
fault exclusion mechanism*:
applicable up to Cat. 3 / PL d
with suitable logic unit
B
10d
NC contact:
2,000,000
B
10d
NO contact at 10% ohmic contact load:
1,000,000
Service life:
20 years
* If a fault exclusion to the 1-channel mechanics is authorised.
MTTF
B
d x
x
h
s/h
3600
d
10d
op
op
op
n
0,1 x n
op
t
cycle
(Determined values can vary depending on the application-specific
parameters h
op
, d
op
and t
cycle
as well as the load.)
If multiple safety components are wired in series, the Performance
Level to ISO 13849-1 will be reduced due to the restricted error
detection under certain circumstances.
3. Mounting
3.1 General mounting instructions
During fitting of the actuator and the sensor, the requirements
of ISO 14119, especially paragraph 7 must be observed!
Four elongated holes are provided for fixing the switch. To facilitate the
alignment of the door to the post, alignment pins are supplied (not for
indoor use) that can be inserted into corresponding holes on the bottom
of the hinge switch (Fig. 2). Once installed, these can be removed again.
Fig. 2
When used in applications with function for the protection of man, the
components must be fitted so that disassembly is prevented (e.g. drill
out the hexagonal recess of the fixing screws, blocking the hexagonal
recess using a plastic cone diameter 5.1 mm).
The hinge switch furthermore must be pinned after assembly and
adjustment (Fig. 3).
A)
A)
Fig. 3
Key
A = Drill and pin in this area
Any mounting position. The mounting position however is chosen so
that the components are preferably fitted in the upper part of the safety
guard to avoid the ingress of dirt and soiling as well as damage to the
components. In case of painting activities, the components must be
covered. Recommended mounting material, see technical data.
We recommend that the fixing screws are painted after the component
is fitted and to apply the accompanying caps (Figure 4.)