schmersal SRB402EM Operating Instructions Manual Download Page 2

2

Operating instructions

Output expander module

SRB402EM

SRB402EM/CC

EN

The entire concept of the control system, in which the safety 

component is integrated, must be validated to EN ISO 13849-2.

There are no residual risks, provided that the safety instructions as well 

as the instructions regarding mounting, commissioning, operation and 

maintenance are observed.

1.6  Warning about misuse

In case of inadequate or improper use or manipulations of 

the component, personal hazards or damage to machinery 

or plant components cannot be excluded. The relevant 

requirements of the standards EN 1088 and EN ISO 13850 

must be observed.

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 

defective mounting or failure to comply with this operating instructions 

manual. The manufacturer shall accept no liability for damages 

resulting from the use of unauthorised spare parts or accessories.

For safety reasons, invasive work on the device as well as arbitrary 

repairs, conversions and modifications to the device are strictly 

forbidden; the manufacturer shall accept no liability for damages 

resulting from such invasive work, arbitrary repairs, conversions and/or 

modifications to the device.

The safety-monitoring module must only be used when the enclosure is 

closed, i.e. with the front cover fitted.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

SRB402EM

No.

Option

Description

plug-in screw terminals 0.25…2.5 mm²

/CC

plug-in cage clamps 0.25 … 1.5 mm²

This device is designed as output expander module. The 

safety function is only realised in conjunction with the basic 

device. To this effect, the device must be connected in  

accordance with the wiring example!

2.2  Special versions

For special versions, which are not listed in the order code below 2.1, 

these specifications apply accordingly, provided that they correspond to 

the standard version.

2.3  Destination and use

The output expander modules for integration in safety circuits are 

designed for fitting in control cabinets. They are used for the safe 

evaluation of the signals and the safe contact multiplication of an 

upstream safety-monitoring module.

The function is defined as the opening of the enabling circuits 13-14,  

23-24, 33-34 and 43-44 when the supply voltage A1-A2 is 

disconnected. The safety-relevant current paths with the output 

contacts 13-14, 23-24, 33-34 and 43-44 meet the following 

requirements under observation of a PFH value assessment  

(also refer to chapter 2.5 "Safety classification"):  

– Control category 4 – PL e to DIN EN ISO 13849-1  

– Corresponds to SIL 3 to DIN EN 61508-2  

– SILCL 3 to DIN EN 62061

To determine the Performance Level (PL) of the entire safety function 

(e.g. sensor, logic, actuator) to DIN EN ISO 13849-1, an analysis of all 

relevant components is required.

2.4  Technical data

General data: 

Standards:

 

IEC/EN 60204-1, EN 60947-5-1;  

EN ISO 13849-1, IEC 61508

Climate resistance:

  

EN 60068-2-78

Mounting:  

Snaps onto standard DIN rail to EN 60715

Terminal designations:

  

EN 60947-1

Material of the housings:

 

Plastic, glass-fibre reinforced 

thermoplastic, ventilated

Material of the contacts: 

AgSnO, self-cleaning, positive drive

Weight:

  

215 g

Start conditions:  

Automatic

Feedback circuit (Y/N):

 yes

Pull-in delay:

 

typ. 30 / max. 45 ms

Drop-out delay:

 

typ. 25 / max. 35 ms

Mechanical data: 

Connection type: 

refer to 2.1 Ordering code

Cable section: 

refer to 2.1 Ordering code

Connecting cable:

  

rigid or flexible

Tightening torque for the terminals:

  

0.6 Nm

With removable terminals (Y/N):

 yes

Mechanical life: 

10 million operations

Electrical life:  

Derating curve available on request

Resistance to shock:

 

10 g / 11 ms

Resistance to vibrations to EN 60068-2-6:

 

10 ... 55 Hz,  

amplitude 0.35 mm

Ambient conditions: 

Ambient temperature:

 

– 25 °C … +45 °C

Storage and transport temperature:

 

– 40 °C … +85 °C

Protection class: 

Enclosure: IP40  

Terminals: IP20  

Clearance: IP54

Air clearances and creepage  

 

distances to IEC/EN 60664-1:

 

4 kV/2 (basic insulation)

EMC rating:  

to EMC Directive

Electrical data: 

Contact resistance in new state:

 

max. 100 mΩ

Power consumption: 

max. 1.0 VA

Rated operating voltage U

e

24 VDC –15% / +20%,  

residual ripple max. 10%,  

24 VAC –15% / +10%

Frequency range: 

50 / 60 Hz

Max. fuse rating of the operating voltage:

 

F1: T 1.0 A / 250 V

Monitored inputs: 

Short-circuit recognition (Y/N): 

No

Wire breakage detection (Y/N):  

Yes

Earth leakage detection (Y/N):  

Yes

Number of NO contacts:

 0

Number of NC contacts:

 0

Conduction resistance:

 

max. 40 Ω

Outputs: 

Number of safety contacts:

 4

Number of auxiliary contacts: 

2

Number of signalling outputs:  

0

Switching capacity of the safety contacts:

  13-14; 23-24; 33-34; 43-44: 

max. 250 V, 6 A ohmic (inductive  

in case of appropriate protective wiring);  

min. 10 V / 10 mA

Switching capacity of the auxiliary contacts:

 

51-52; 61-62:  

24 VDC / 2 A

Fuse rating of the safety contacts

external (I

k

 = 1000 A)  

to EN 60947-5-1  

8 A quick blow, 6 A slow blow

Fuse rating for the auxiliary contacts: 

external (I

k

 = 1000 A)  

to EN 60947-5-1  

Safety fuse 2.5 A quick blow, 2 A slow blow

Utilisation category to IEC/EN 60947-5-1:

 

AC-15: 230 VAC / 6 A  

DC-13: 24 VDC / 6 A 

Summary of Contents for SRB402EM

Page 1: ...eloped to execute safety related functions as part of an entire plant or machine It is the responsibility of the manufacturer of a machine or plant to ensure the correct functionality of the entire machine or plant The output expander module must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding th...

Page 2: ...and 43 44 meet the following requirements under observation of a PFH value assessment also refer to chapter 2 5 Safety classification Control category 4 PL e to DIN EN ISO 13849 1 Corresponds to SIL 3 to DIN EN 61508 2 SILCL 3 to DIN EN 62061 To determine the Performance Level PL of the entire safety function e g sensor logic actuator to DIN EN ISO 13849 1 an analysis of all relevant components is...

Page 3: ... enclosure slightly tilted forwards in the DIN rail and push up until it latches in position 3 2 Dimensions All measurements in mm Device dimensions H W D SRB402EM 120 22 5 121 mm SRB402EM CC 130 22 5 121 mm 4 Electrical connection 4 1 General information for electrical connection As far as the electrical safety is concerned the protection against unintentional contact of the connected and therefo...

Page 4: ...be disassembled in the de energised condition only Push up the bottom of the enclosure and hang out slightly tilted forwards 7 2 Disposal The output expander module must be disposed of in an appropriate manner in accordance with the national prescriptions and legislations 8 Appendix 8 1 Wiring example Single channel control at terminal A1 of the SRB402EM expander module through a safety release of...

Page 5: ...age Directive EMC Directive RoHS Directive 2006 95 EC 2004 108 EC 2011 65 EU 2014 35 EU 2014 30 EU 2011 65 EU Applied standards EN 60947 5 1 2004 AC 2005 A1 2009 Place and date of issue Wuppertal April 13 2016 Authorised signature Philip Schmersal Managing Director EU Declaration of conformity Original K A Schmersal GmbH Co KG Möddinghofe 30 42279 Wuppertal Germany Internet www schmersal com We he...

Page 6: ...o KG Industrielle Sicherheitsschaltsysteme Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com ...

Reviews: