
4
Operating instructions
Safety-monitoring module
SRB 301ST-230V
EN
6. Set-up and maintenance
6.1 Functional testing
The safety function of the safety-monitoring module must be tested.
The following conditions must be previously checked and met:
1. Correct fixing
2. Check the integrity of the cable entry and connections
3. Check the safety-monitoring module's enclosure for damage.
4. Check the electrical function of the connected sensors and their
influence on the safety-monitoring module and the downstream
actuators
6.2 Maintenance
A regular visual inspection and functional test, including the following
steps, is recommended:
1. Check the correct fixing of the safety-monitoring module
2. Check the cable for damages
3. Check electrical function
The device has to be integrated into the periodic check-ups
according to the Ordinance on Industrial Safety and Health,
however at least 1 × year.
Damaged or defective components must be replaced.
7. Disassembly and disposal
7.1 Disassembly
The safety-monitoring module must be disassembled in a de-energised
condition only.
Push up the bottom of the enclosure and hang out slightly tilted
forwards.
7.2 Disposal
The safety-monitoring module must be disposed of in an appropriate
manner in accordance with the national prescriptions and legislations.
8. Appendix
8.1 Wiring examples
Dual-channel control, shown for a guard door monitor with two
position switches A and B where one has a positive break contact;
with external reset button
J
(Fig. 2)
• Relay outputs: Suitable for 2-channel control, for increase in capacity
or number of contacts by means of contactors or relays with positive-
guided contacts.
• The control system recognises wire-breakage in the monitoring circuit.
•
S
= Feedback circuit
S12 S11 S21
J
S22 X3 X2
K
B
K
A
K
A
K
B
K2
K1
A2
14
N
24 34 42
S
a)
K1
K2
Ui
F1
13
23 33
L1
41
A1
A
B
AC
DC
Fig. 2 a) Logic
8.2 Start configuration
External reset button (with edge detection) (see Fig. 3)
• The external reset button is integrated as shown.
• The safety-monitoring module is activated by the reset (after release)
of the reset button (= detection of the trailing edge). Faults in the reset
button, e.g. welded contacts or manipulations which could lead to an
inadvertent restart, are detected in this configuration and will result in
an inhibition of the operation.
Automatic start (see Fig. 4)
• The automatic start is programmed by connecting the feedback
circuit to the terminals. If the feedback circuit is not required,
establish a bridge.
• Caution: Not admitted without additional measure due to the risk of
gaining access by stepping behind!
• Caution: within the meaning of EN IEC 60204-1 paragraph 9.2.5.4.2,
the operating mode "automatic start" is only restrictedly admissible. In
particular, any inadvertent restart of the machine must be prevented
by other suitable measures.
K
B
J
S
K
A
X2
S12
K
B
S
K
A
X3
S12
Fig. 3
Fig. 4