SRB 301AN

Operating instructions

Safety-monitoring module

EN

Protection of the safety contacts:

 

external (I

k

 = 1000 A)  

to EN 60947-5-1  

Safety fuse 8 A quick blow, 6 A slow blow

Fuse rating of the signalling output:

 

Y1: 500 mA (internal  

electronic fuse)

Utilisation category to EN 60947-5-1:

 

AC-15 / DC-13: EN 60947-5-1

Dimensions (H x W x D): 

100 x 22.5 x 121 mm

The data specified in this manual are applicable when the  

component is operated with rated operating voltage U

e

 ±0%.

2.5   Safety classification

Standards:

 

EN ISO 13849-1, IEC 61508, EN 60947-5-1

PL:

 

up to e

Control category:

 

up to 4

DC: 

99% (high)

CCF: 

> 65 points

PFH value:

 

≤ 2.00 × 10

-8

/h

SIL:

 

up to 3

Service life:

 

20 years

The PFH value of 2.00 × 10

-8

/h applies to the combinations of contact 

load (current through enabling contacts) and number of switching cy-

cles (n

op/y

) mentioned in the table below. At 365 operating days per year 

and a 24-hours operation, this results in the below-mentioned switching 

cycle times (t

cycle

) for the relay contacts.

Diverging applications upon request.

Contact load

n

op/y

t

cycle

20 %

525,600

1.0 min

40 %

210,240

2.5 min

60 %

75,087

7.0 min

80 %

30,918

17.0 min

100 %

12,223 

43.0 min

3.  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.

Snap the bottom of the enclosure slightly tilted forwards in the DIN rail 

and push up until it latches in position.

3.2  Dimensions

All measurements in mm.

Device dimensions (H/W/D): 100 x 22.5 x 121 mm

4.  Electrical connection

4.1  General information for electrical connection

As far as the electrical safety is concerned, the protection 

against unintentional contact of the connected and therefore 

electrically interconnected apparatus and the insulation of the 

feed cables must be designed for the highest voltage, which 

can occur in the device.

The electrical connection may only be carried out by autho-

rised personnel in a de-energised condition.

Wiring examples: see appendix

5.  Operating principle and settings

5.1  LED functions

•  K1: Status channel 1

•  K2: Status channel 2

•  U

i

: Status internal operating voltage (LED is on, when the operating 

voltage on the terminals A1-A2 is ON and the fuse has not been  

triggered).

5.2  Description of the terminals

Voltages:

A1
A2

+24 VDC/24 VAC 
0 VDC/0 VAC

Inputs:

S13 - S14
S21 - S22

Input channel 1
Input channel 2

Outputs:

13 - 14
23 - 24
33 - 34
Y1

First safety enabling circuit
Second safety enabling circuit
Third safety enabling circuit
Signalling output

Start:

X1 - X2

X1 - X3

Feedback circuit and external reset 
(monitored)
Automatic start

K1
U

i

K2

SRB 

301AN

13 23 33 Y1
A1 X1 X2 X3

14 24 34 S13

A2 S21 S22 S14

Fig. 1

5.3  Notes

Signalling outputs must not be used in safety circuits.

Due to the operating principle of the electronic fuse, the cus-

tomer must check that no hazard is caused by an unexpected 

restart in circuits without reset button (automatic reset).