background image

4

Operating instructions

Safety sensor

EX-BNS 303-2187

EN

4.  Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by 

authorised personnel in a de-energised condition.

The safety sensors must be wired in accordance with the specified  

wire colours.

4.2  Contact variants

The contact position shows the actuated sensor function when the 

safety guard is closed.

1 NO contacts / 2 NC contacts

with LED

EX-BNS 303-12Z-2187-3G/D

EX-BNS 303-12ZG-2187-3G/D

GY 13

GN 21

WH 31

14 PK

22 YE

32 BN

GY 13

GN 21

WH 31

14 PK

32 BN

22 YE

4.3  Connection

For safety-monitoring modules with two NC inputs, the wires of the 

safety sensor must be wired as follows:

NO contacts: GY (13) and PK (14) 

at the "NO input" of the  

safety-monitoring module

NC contacts: GN (21) und YE (22)

at the "NC input" of the  

safety-monitoring module

NC contacts: WH (31) und BN (32)

can be used for signalling  

purposes.

Information for the selection of suitable safety-monitoring 

modules can be found in the Schmersal catalogues or in the 

online catalogue on our website: www.schmersal.net.

Technically, multiple safety sensors can be wired to one AES safety-

monitoring module (check if authorised!). The NO contacts are wired 

parallel and the NC contacts in series. The input expander modules 

PROTECT-IE-11 and -02 or PROTECT-PE-11(-AN) and -02 can be 

used for joint connection up to 4 safety sensors with NC/NC or NC/NO 

contacts.

Connecting more than two EX-BNS 303-12Z safety sensors to the  

AES 7112 or AES 1102/1112 safety-monitoring module is not 

possible. For connecting only one safety sensor: refer to the operating 

instructions manual of the AES 7112 or AES 1102/1112.

 

Safety sensors equipped with LED's shall not be wired in series, except 

for the PROTECT-IE or PROTECT-PE input expander module. As a 

result of this, the luminosity of the LED's would considerably decrease 

and the voltage could drop below the minimum input voltage of the 

downstream safety-monitoring module. 

In case of series-wiring at SRB max. 1 sensor with LED indication for U

N

.

5.  Set-up and maintenance

5.1  Functional testing

The safety function of the safety components must be tested. 

The following conditions must be previously checked and met:

1. The installation is executed according to the instructions

2. The connection is executed correctly

3. The safety component is not damaged

4.  The system is free of dirt and soiling (in particular metal chips)

5.  Check cable entry and connections in a de-energised condition

5.2  Maintenance

In the case of correct installation and adequate use, the safety sensor 

features maintenance-free functionality. A regular visual inspection and 

functional test, including the following steps, is recommended:

• Check the fitting of the sensor and the actuator

• Remove possible metal chips

• Check the cable for damage.

•  Check cable entry and connections in de-energised condition

Adequate measures must be taken to ensure protection 

against tampering either to prevent tampering of the safety 

guard, for instance by means of replacement actuators.

Damaged or defective components must be replaced.

6.  Disassembly and disposal

6.1  Disassembly

The safety switchgear must be disassembled in a de-energised 

condition only.

6.2  Disposal

The safety switchgear must be disposed of in an appropriate manner  

in accordance with the national prescriptions and legislations.

Reviews: