schmersal CSS 30S Operating Instructions Manual Download Page 5

5

CSS 30S

CSS 300

Operating instructions

Safety sensor

EN

6.2  Operating principle of the electronic diagnostic output

The short-circuit proof diagnostic output can be used for central 

visualisation or control functions, e.g. in a PLC.

The electronic diagnostic output signals faults before the safety outputs 

are disabled, thus enabling a controlled shutdown.

The diagnostic output is not a safety-related output!

The diagnostic output can also be used to detect clearance variations 

between the sensor and the actuator in the same way as the yellow 

LED. An active fault causes the diagnostic output to be disabled.  The 

safety outputs are disabled after max. 30 minutes if the fault is not 

rectified. The signal combination, diagnostic output disabled and safety 

channels still enabled, can be used to stop the production process in a 

controlled manner.

Error

A fault has occurred, which causes the safety outputs to be disabled. 

The fault is reset, when the cause is eliminated and bit 7 of the request 

byte changes from 1 to 0 or the safety guard is opened. Faults at the 

safety outputs are only deleted upon the next release, as the fault 

rectification cannot be detected sooner.

Error warning

A fault has occurred, which causes the safety outputs to be disabled 

after 30 minutes. The safety outputs initially remain enabled. This 

enables the shutdown of the process in a controlled manner. An error 

warning is deleted when the cause of error is eliminated.

Table 1:  Examples of the diagnostic function of the safety-sensor with conventional diagnostic output

System condition

Duo LED

green  red

LED

yellow

Diagnostic 

output

Safety  

outputs  

Y1, Y2

Note

Supply voltage on, not actuated

On

Off

Off

0 V

0 V

Voltage on, no evaluation of the voltage quality

Actuated

On

Off

On

24 V

24 V

The yellow LED always signals the presence of an 
actuator within range

Actuated in limit area

On

Off

Flashes

24 V 

pulsed

24 V

The sensor must be adjusted before the distance to 
the actuator increases and before the safety outputs 
are disabled, thus stopping the machine

Actuator, error warning

Off

Flashes

On

0 V

24 V

The safety outputs are disabled after 30 minutes  
if the error is not rectified.

Actuated, fault

Off

Flashes

On

0 V

0 V

Refer to table with flash codes

Actuated, internal fault

Off

On

On

0 V

0 V

---

6.3  Safety-sensors with serial diagnostic function

Safety sensors with serial diagnostic cable have a serial input and 

output cable instead of the conventional diagnostic output. If safety 

sensors are wired in series, the safety channels as well as the inputs 

and outputs of the diagnostic channels are wired in series.

Max. 31 sensors can be wired in series. For the evaluation of the serial 

diagnostics line either the PROFIBUS-Gateway SD-I-DP-V0-2 or the 

Universal-Gateway SD-I-U-… are used.  This serial diagnostic interface 

is integrated as a slave in an existing field bus system.  In this way, the 

diagnostic signals can be evaluated by means of a PLC. The necessary 

documentation for the integration of the SD-Gateway is available for 

download at www.schmersal.com.

Accessories SD interface

For ease of wiring and series-wiring of SD devices,  

considerable accessories are available. Detailed information 

is available on the Internet, www.schmersal.net. 

The response data and the diagnostic data are automatically and 

permanently written in the assigned input byte of the PLC for each 

safety sensor in the series-wired chain. The request data for each 

safety sensor are transmitted to the device through an output byte of 

the PLC.

In the event of a communication error between the field bus Gateway 

and the safety sensor, the switching condition of the safety output of the 

safety sensor is maintained.

Summary of Contents for CSS 30S

Page 1: ...for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user m...

Page 2: ...tput channel The serial connections of the individual sensors are wired in series together with other devices and connected to a Field Bus Gateway Mode of operation of the safety outputs The opening o...

Page 3: ...s 30 Nm CSS 30S or 400 Ncm CSS 300 A concealed mounting is possible however this reduces the switching distance The reduction will be lower when the sensor and the actuator protrudes a few mm The actu...

Page 4: ...cables must be taken as large as possible Wiring examples for series wiring refer to appendix Protection is not required when pilot wires are laid The cables however must be separated from the supply...

Page 5: ...Actuated On Off On 24 V 24 V The yellow LED always signals the presence of an actuator within range Actuated in limit area On Off Flashes 24 V pulsed 24 V The sensor must be adjusted before the dista...

Page 6: ...C to the local safety sensor Response byte from the local safety sensor to the PLC Warning error byte from the local safety sensor to the PLC Bit n Request byte Response byte Diagnostic error warning...

Page 7: ...s Gateway is connected to the serial diagnostic input of the first sensor 24VDC GND 1 2 3 5 4 6 8 X1 Y1 X2 SD IN SD OUT A1 A2 1 2 3 5 4 6 8 X1 Y1 X2 7 Y2 7 Y2 SD IN SD OUT A1 A2 X1 Y1 X2 Y2 SDIN SDOUT...

Page 8: ...elevant Directives Machinery Directive EMC Directive RoHS Directive 2006 42 EC 2014 30 EU 2011 65 EU Applied standards EN 60947 1 2007 A1 2011 EN 60947 5 3 2013 ISO 14119 2013 EN ISO 13849 1 2008 AC 2...

Reviews: