background image

6

Operating instructions

Control panel with emergency stop

BDF200-SD

BDF200-FB

EN

6.  Diagnostic functions

6.1  Diagnostic functions of SD interface

Safety switchgear devices with serial diagnostic cable have a serial 

input and output instead of the conventional diagnostic output If these 

safety switchgear devices are wired in series, the safety channels as 

well as the inputs and outputs of the diagnostic channels are wired in 

series

Up to 31 safety switchgear devices can be connected in series with 

serial diagnostics For the evaluation of the serial diagnostics line either 

the PROFIBUS-Gateway SD-I-DP-V0-2 or the Universal-Gateway  

SD-I-U- are used This SD-Gateway is integrated as a slave in an 

existing field bus system In this way, the diagnostic signals can be 

evaluated by means of a PLC

The necessary documentation for the integration of the SD-Gateway is 

available for download at wwwschmersalcom

The query details for each safety sensor are transmitted to the device 

via one output byte of the PLC respectively

The request data for each safety sensor are transmitted to the device 

through an output byte of the PLC

Should a communication error occur between the SD Gateway and the 

safety switchgear, the safety switchgear retains its switch status for the 

safety outputs

Diagnostic error warning and error

If an error (warning) is signalled in the response byte, detailed fault 

information can be read out

Detailed information about the use of the serial diagnostics can be 

found in the operating instructions of the PROFIBUS-Gateway  

SD-I-DP-V0-2 and the Universal-Gateway SD-I-U-….

Error warning

A fault has occurred, which causes the safety outputs to be disabled 

after 30 minutes The safety outputs initially remain enabled  

This enables the shutdown of the process in a controlled manner  

An error warning is deleted when the cause of error is eliminated

Error

A fault has occurred, which causes the safety outputs to be disabled 

The fault is reset, when the cause is eliminated and bit 7 of the query 

byte changes from 1 to 0 or the emergency stop is pressed again 

Faults at the safety outputs are only deleted upon the next release,  

as the fault rectification cannot be detected sooner

On the FB variant of the BDF200-SD/FB, the two diagnosis 

bytes 'Error warnings' and 'Error messages' are not 

transferred

Table 1: Overview of status signals, warnings or error messages of SD variant

Communication directions: Request byte:

From PLC to local safety switchgear

Response byte:

From local safety switchgear to PLC

Warning/error byte:

From local safety switchgear to PLC

Bit n°  Request byte

Response byte

Diagnostic
Error warnings

Error messages

Bit 0: —

Safety output  
emergency stop switched on

Error output Y1

Error output Y1

Bit 1: LED G24 red

NO contact from  

pos 2

Error output Y2

Error output Y2

Bit 2: LED G24 green

NC contact from  

pos 2

Cross-wire Y1/Y2

Cross-wire Y1/Y2

Bit 3: LED illuminated push button pos 2 NO contact from 

pos 3

Temperature too high

Temperature too high

Bit 4: LED illuminated push button pos 3 NC contact from  

pos 3

Error emergency stop button

Bit 5: LED illuminated push button pos 4 NO contact from  

pos 4

Internal device error

Internal device error

Bit 6: —

Error warning

Communication error between field 
bus Gateway and SD slave

Bit 7: Error reset

Error  
(enabling path switched off)

Operating voltage limit

7.  Set-up and maintenance

7.1  Functional testing

The safety function of the safety components must be tested  

The following conditions must be checked and met:

• Correct fixing of the fitted component

• Check the integrity of the cables and connections

• Check the command and signalling devices for damage

•  For the types with extension …-2875, the proper fitting and the 

smooth operation of the pushbuttons must be checked after the 

installation of the pushbutton and illuminated pushbutton caps

7.2  Maintenance

The function of the emergency stop button must be tested in regular 

intervals

Maintenance:

 Please observe that the safety function must 

be triggered at least once a year to test the system!

In case of correct installation in accordance with the instructions 

described above, the component requires little maintenance Under 

extreme conditions, we recommend routine maintenance as follows:

• Check the correct fixing of the control panel

• Remove particles of dust and soiling

• Check the integrity of the cables and connections

•  For the types with extension …-2875, the smooth operation of the 

pushbuttons and the illuminated pushbuttons must be checked

Damaged or defective components must be replaced.

8.  Disassembly and disposal

8.1  Disassembly

The safety switchgear must be disassembled in a de-energised 

condition only

8.2  Disposal

The safety switchgear must be disposed of in an appropriate manner in 

accordance with the national prescriptions and legislations

Summary of Contents for BDF200-FB

Page 1: ...version in the vicinity of the device 1 2 Target group authorised qualified personnel All operations described in this operating instructions manual must be carried out by trained specialist personne...

Page 2: ...ained selector switch 2 or 3 positions WT 2 3 Maintained spring return rotary selector switch 2 or 3 positions SWS SWT 20 Key operated selector switch 2 positions Pos 4 Command and signalling device L...

Page 3: ...urce has to be an isolated secondary source limited by a Listed fuse rated 4A min 24VAC DC Adapters providing field wiring means are available from the manufacturer Refer to manufacturer s information...

Page 4: ...e rating of a device chain for protection of the cable depends on the cross section of the cables used Requirements for the connected safety monitoring module Dual channel safety input suitable for p...

Page 5: ...n of the command and signalling devices The non safety signals of the command devices are transmitted to the control system via the response byte in the SD FB protocol The Illuminated signals are cont...

Page 6: ...ges are not transferred Table 1 Overview of status signals warnings or error messages of SD variant Communication directions Request byte From PLC to local safety switchgear Response byte From local s...

Page 7: ...K BK OUT SD output 5 GY GY GY X2 Safety input 2 6 PK VT PK Y2 Safety output 2 7 BU RD VT IN SD input 8 RD PK OR Connector plug M12 8 pole A coded 9 2 Pin assignment FB variant Function safety switchge...

Page 8: ...ED illuminated push button pos 4 Bit 6 Bit 7 Error reset PLC input data BDF200 FB BDF200 FB SFB PLC Device module SFB module data_1 Sub module Diagnosis and FB interface 6 byte input Slot PROFINET Eth...

Page 9: ...BDF200 SD BDF200 FB Type See ordering code Description of the component Control panel with emergency stop and integrated SD interface or FB interface Relevant Directives 2006 42 EG 2014 30 EU 2011 65...

Page 10: ...A Schmersal GmbH Co KG M ddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal c...

Reviews: