background image

8

Operating instructions

Control panel with emergency stop

BDF200-SD

BDF200-FB

EN

9.3  Field bus data FB variant

PLC output data BDF200-FB 

(PLC → SFB → BDF200-FB

)

- Device module: 

SFB module data_1

- Sub module: 

 Diagnosis and FB interface 

4 byte output

Slot

PROFINET

EtherNet/IP

Output data

Output data

4

Slot: 

1 3

Byte: n

Assembly 301
- Byte 2

5

Slot: 

1 3

Byte: 

n + 1

Assembly 301
- Byte 3

6

Slot: 

1 3

Byte: 

n + 2

Assembly 301
- Byte 4

7

Slot: 

1 3

Byte: 

n + 3

Assembly 301
- Byte 5

Bit assignment output data

Bit n°

 Request byte

Bit 0:

---

Bit 1:

LED G24 red

Bit 2:

LED G24 green

Bit 3:

LED illuminated push button pos 2

Bit 4:

LED illuminated push button pos 3

Bit 5:

LED illuminated push button pos 4

Bit 6:

---

Bit 7:

Error reset

PLC input data BDF200-FB (BDF200-FB

 → 

SFB

 → 

PLC)

- Device module: 

SFB module data_1

- Sub module: 

 Diagnosis and FB interface 

6 byte input

Slot

PROFINET

EtherNet/IP

Input data

Input data

4

Slot: 

1 3

Byte: 

n + 2

Assembly 300
- Byte 6

5

Slot: 

1 3

Byte: 

n + 3

Assembly 300,
- Byte 7

6

Slot: 

1 3

Byte: 

n + 4

Assembly 300
- Byte 8

7

Slot: 

1 3

Byte: 

n + 5

Assembly 300
- Byte 9

Bit assignment input data

Bit n°

Response byte

Bit 0:

Safety output emergency stop switched on

Bit 1:

NO contact from  

pos 2

Bit 2:

NC contact from  

pos 2

Bit 3:

NO contact from 

pos 3

Bit 4:

NC contact from  

pos 3

Bit 5:

NO contact from  

pos 4

Bit 6:

Error warning

Bit 7:

Error (enabling path switched off)

Detailed information about the field bus data and  

bit assignment can be found in the system handbook  

"Safety field box SFB" at wwwschmersalnet

Summary of Contents for BDF200-FB

Page 1: ...version in the vicinity of the device 1 2 Target group authorised qualified personnel All operations described in this operating instructions manual must be carried out by trained specialist personne...

Page 2: ...ained selector switch 2 or 3 positions WT 2 3 Maintained spring return rotary selector switch 2 or 3 positions SWS SWT 20 Key operated selector switch 2 positions Pos 4 Command and signalling device L...

Page 3: ...urce has to be an isolated secondary source limited by a Listed fuse rated 4A min 24VAC DC Adapters providing field wiring means are available from the manufacturer Refer to manufacturer s information...

Page 4: ...e rating of a device chain for protection of the cable depends on the cross section of the cables used Requirements for the connected safety monitoring module Dual channel safety input suitable for p...

Page 5: ...n of the command and signalling devices The non safety signals of the command devices are transmitted to the control system via the response byte in the SD FB protocol The Illuminated signals are cont...

Page 6: ...ges are not transferred Table 1 Overview of status signals warnings or error messages of SD variant Communication directions Request byte From PLC to local safety switchgear Response byte From local s...

Page 7: ...K BK OUT SD output 5 GY GY GY X2 Safety input 2 6 PK VT PK Y2 Safety output 2 7 BU RD VT IN SD input 8 RD PK OR Connector plug M12 8 pole A coded 9 2 Pin assignment FB variant Function safety switchge...

Page 8: ...ED illuminated push button pos 4 Bit 6 Bit 7 Error reset PLC input data BDF200 FB BDF200 FB SFB PLC Device module SFB module data_1 Sub module Diagnosis and FB interface 6 byte input Slot PROFINET Eth...

Page 9: ...BDF200 SD BDF200 FB Type See ordering code Description of the component Control panel with emergency stop and integrated SD interface or FB interface Relevant Directives 2006 42 EG 2014 30 EU 2011 65...

Page 10: ...A Schmersal GmbH Co KG M ddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal c...

Reviews: