background image

5

BDF 200 AS

Operating instructions
Control panel with emergency stop

EN

5.5  Programming the slave address

The slave addresses for both integrated
AS-i slaves are programmed through the M12 connector 

To that effectn the lower enclosure cover must be opened By means 
of the there-located DIP switches, both AS-i slaves can be individually 
separated from or connected to the AS-i connection

• DIP-SW 1 

AS-i A/B-Slave 

• DIP-SW 2 

AS-i Safety-Slave

For the AS-i Safety-Slave an address from 1 to 31 and for the AS-i A/B 
slave an adress from 1A to 31B can be set by means of an AS-i bus 
master or a hand-held programming device

ON

1

2

DIP-SW 1: 

AS-i A/B-Slave 

DIP-SW 2:  AS-i Safety-Slave

Caution!

  

Do not touch electrostatically loaded elements  
Do not touch the printed circuit board

5.6  Status signal "safety release"

The "safety release" status signal from a Safety at Work slave can be 
cyclically queried by the control system through the AS-i master To 
thiseffect, the 4 input bits with the varying SaW code of a Safety at 
Work slave are evaluated through an OR operation with 4 inputs in the 
control system

6.  Set-up and maintenance

6.1  Functional testing

The safety function of the safety components must be tested The 
following conditions must be checked and met: 

• Correct fixing of the fitted component

• Check the integrity of the cables and connections

• Check the command and signalling devices for damage

6.2  Maintenance

The function of the emergency stop button must be tested in regular 
intervals

Maintenance:

 Please observe that the safety function must 

be triggered at least once a year to test the system!

In case of correct installation in accordance with the above-described 
instructions, the component requires little maintenance Under extreme 
conditions, we recommend routine maintenance as follows:

• Check the correct fixing of the control panel

• Remove particles of dust and soiling.

• Check the integrity of the cables and connections

Damaged or defective components must be replaced.

7.  Disassembly and disposal

7.1  Disassembly

The safety switchgear must be disassembled in a de-energised  
condition only

7.2  Disposal

The safety switchgear must be disposed of in an appropriate manner in 
accordance with the national prescriptions and legislations

Reviews: