schmersal AZM300Z-I1-ST1P2P-A-T Instructions For Assembly And Operation Manual Download Page 4

without

Power to unlock

A

Power to lock

(5)

without

Manual release

N

Emergency release

T

Emergency exit

T 8

Emergency exit, distance 8.5 mm

2.2 Special versions

For special versions, which are not listed in the ordering code, these specifications apply accordingly, provided that
they correspond to the standard version.

2.3 Purpose

The non-contact, electronic safety switchgear is designed for application in safety circuits and is used for monitoring
the position and locking of movable safety guards.

F

The safety switchgears are classified according to EN ISO 14119 as type 4 interlocking devices. Designs with individual coding
are classified as highly coded.

The different variants can be used as safety switch with interlocking function either as solenoid interlock.

2

If the risk analysis indicates the use of a 

monitored interlock

 then a variant with the monitored interlock is to be used,

marked with the 

>

 symbol in the ordering code.

The actuator monitoring variant (B) is a safety switch with an interlock function for process protection.

The safety function consists of safely switching off the safety outputs when the safety guard is unlocked or opened and
maintaining the safe switched off condition of the safety outputs for as long as the safety guard is open.

2

Interlocks with power to lock principle may only be used in special cases after a thorough evaluation of the accident risk, since
the safety guard can be opened immediately on failure of the power supply or upon activation of the main switch.

Series-wiring

Series-wiring can be set up. In the case of a series connection, the risk time remains unchanged and the reaction time
increases by the sum of the reaction time of the inputs per additional unit specified in the technical data. The quantity
of devices is only limited by the cable drops and the external cable fuse protection, according to the technical data. Up
to 31 device variants with serial diagnostics can be wired in series.

Summary of Contents for AZM300Z-I1-ST1P2P-A-T

Page 1: ...e 3 3 Emergency exit T T8 or emergency release N 3 4 Mounting with mounting plate 3 5 Dimensions 3 6 Actuator and accessories 4 Electrical connection 4 1 General information for electrical connection...

Page 2: ...ations regarding occupational safety and accident prevention prior to installation and putting the component into operation The machine builder must carefully select the harmonised standards to be com...

Page 3: ...iption 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety...

Page 4: ...is to be used marked with the symbol in the ordering code The actuator monitoring variant B is a safety switch with an interlock function for process protection The safety function consists of safely...

Page 5: ...ulting from defective mounting or failure to comply with the operating instructions manual The manufacturer shall accept no liability for damages resulting from the use of unauthorised spare parts or...

Page 6: ...Yes Number of fail safe digital outputs 2 Safety classification Standards EN ISO 13849 1 EN IEC 61508 Safety classification Interlocking function Performance Level up to e Category 4 PFH value 5 20 x...

Page 7: ...ightening torque of the fixing screws maximum 7 Nm Mechanical data Switching distances according EN IEC 60947 5 3 Assured switching distance ON S ao 1 mm Assured switching distance OFF S ar 20 mm Swit...

Page 8: ...values Rated insulation voltage U i 32 VDC Rated impulse withstand voltage U imp 0 8 kV Overvoltage category III Degree of pollution to IEC EN 60664 1 3 Electrical data Operating voltage minimum 20 4...

Page 9: ...ms Classification ZVEI CB24I Sink C1 Classification ZVEI CB24I Source C1 C2 C3 Electrical data Safety digital outputs Designation Safety outputs Y1 and Y2 Design of control elements short circuit pro...

Page 10: ...serial diagnostics SD2P is not allowed due to the non safe locking unlocking signal from the SD Gateway 2 If for a certain application the power to unlock version of a solenoid interlock cannot be us...

Page 11: ...llowing two conditions 1 This device may not cause harmful interference and 2 This device must be able to tolerate interfering signals This includes interfering signals that may cause the unit not to...

Page 12: ...d be reduced Mounting of the solenoid interlock and the actuator Refer to the mounting instructions manual for the corresponding actuator 2 The actuator must be permanently fitted to the safety guards...

Page 13: ...orrect False To avoid any interference inherent to this kind of system and any reduction of the switching distances please observe the following guidelines The presence of metal chips in the vicinity...

Page 14: ...mm 3 2 Manual release For the machine set up the solenoid interlock can be unlocked in a de energised condition The solenoid interlock is unlocked by turning the manual release in the position qThe no...

Page 15: ...fter completing commissioning 3 3 Emergency exit T T8 or emergency release N With variants that have both emergency exit and emergency release the red lever is loosely supplied Before first use mount...

Page 16: ...at it should only be used in an emergency The label can be used that was included in the delivery To activate the emergency release turn the red lever in the direction of the arrow to the end stop The...

Page 17: ...3 5 Dimensions All measurements in mm AZM300 T T8 and N Device with emergency exit or emergency release Emergency exit T Emergency release N...

Page 18: ...Emergency exit T8 3 6 Actuator and accessories Actuator AZ AZM300 B1 not included in delivery Mounting plate MP AZ AZM300 1 available as accessory...

Page 19: ...MS AZ AZM300 B1 1 available as accessory Aluminium protective plate as a cover for use on glass and plastic doors on machines with high design requirements Lockout tag SZ 200 1 available as accessory...

Page 20: ...n cable release 4 Electrical connection 4 1 General information for electrical connection 2 The electrical connection may only be carried out by authorised personnel in a de energised condition The vo...

Page 21: ...op on the cables and the current carrying capacity of the individual components F Accessories for the series wiring For convenient wiring and series wiring of SD components the SD junction boxes PFB S...

Page 22: ...serial diagnostics connections are wired in series and connected to a SD Gateway for evaluation purposes The safety outputs of the first safety component are wired to the safety monitoring module The...

Page 23: ...SD output 5 GY GY GY X2 Safety input 2 6 PK VT PK Y2 Safety output 2 7 BU RD VT IN Solenoid control SD input 8 RD PK OR Connecting cables with coupling female IP67 IP69 M12 8 pole 8 x 0 25 mm to DIN 4...

Page 24: ...an unlimited number of times When a new actuator is taught the code which was applicable until that moment becomes invalid Subsequent to that an enabling inhibit will be active for ten minutes thus p...

Page 25: ...it upstream is open Flashes 1 Hz Off On 6 4 Solenoid interlock with conventional diagnostic output The short circuit proof diagnostic output OUT can be used for central visualisation or control tasks...

Page 26: ...be locked or fault Legend Safety guard open Safety guard closed Locking time Safety guard not locked or fault Safety guard locked Lock Unlock Evaluation of diagnostic output Power to unlock IN 0 Lock...

Page 27: ...king impossible 0 V 24 V On Off Flashes 0 V 24 V 0 V Safety guard closed and locked 0 V 24 V On Off On 24 V 24 V 24 V Error warning1 0 V 24 V On Flashes 2 On 24 V1 24 V1 0 V Error 0 V 24 V 24 V 0 V On...

Page 28: ...d as slave in an existing field bus system In this way the diagnostic signals can be evaluated by means of a PLC The necessary software for the integration of the SD Gateway is available for download...

Page 29: ...be unlocked if e g the door pulls the turret out of its rest position beyond the set latching force This can occur if doors are heavily distorted or when pulling the door The solenoid interlock can o...

Page 30: ...ns of replacement actuators 2 Damaged or defective components must be replaced 8 Disassembly and disposal 8 1 Disassembly The safety switchgear must be disassembled in a de energised condition only 8...