7
AZM 200
Operating instructions
Solenoid interlock
EN
Table 3: I/O data and diagnostic data
Bit n°
Request byte
Response byte
Diagnostic error warning
Diagnostic error
Bit 0:
Magnet in, irrespective of
power to lock or power to
unlock principle
Safety output activated
Error output Y1
Error output Y1
Bit 1:
---
Actuator detected
Error output Y2
Error output Y2
Bit 2:
---
Actuator detected and locked
Cross-wire short
Cross-wire short
Bit 3:
---
---
Temperature too high
Temperature too high
Bit 4:
---
Input condition X1 and X2
---
incorrect or
defective actuator
Bit 5:
---
Guard door detected
Internal device error
Internal device error
Bit 6:
---
Error warning
1)
Communication error between the field
bus Gateway and the safety switchgear
---
Bit 7:
Error reset
Error
(enabling path switched off)
Operating voltage too low
---
1)
after 30 min -> fault
The described condition is reached, when Bit = 1
7. Set-up and maintenance
7.1 Functional testing
The safety function of the safety components must be tested.
The following conditions must be previously checked and met:
1. Fitting of the solenoid interlock and the actuator
2. Check the integrity of the cable entry and connections
3. Check the switch enclosure for damage
7.2 Maintenance
We recommend a regular visual inspection and functional test, including
the following steps:
1. Check for tight installation of the actuator and the switch
2. Remove particles of dust and soiling
3. Check cable entry and connections
Adequate measures must be taken to ensure protection
against tampering either to prevent tampering of the safety
guard, for instance by means of replacement actuators.
Damaged or defective components must be replaced.
8. Disassembly and disposal
8.1 Disassembly
The safety switchgear must be disassembled in a de-energised
condition only.
8.2 Disposal
The safety switchgear must be disposed of in an appropriate manner
in accordance with the national prescriptions and legislations.