Operating instructions
Solenoid interlock

AZM 161../..

EN

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 
defective mounting or failure to comply with this operating instructions 
manual. The manufacturer shall accept no liability for damages result-
ing from the use of unauthorised spare parts or accessories.

For safety reasons, invasive work on the device as well as arbitrary re-
pairs, conversions and modifications to the device are strictly forbidden; 
the manufacturer shall accept no liability for damages resulting from 
such invasive work, arbitrary repairs, conversions and/or modifications 
to the device.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

AZM 161 

-

➁➂

 K

-

/

-

➆➇

No.

Option

Description

CC

Cage clamps

SK

Screw connection

ST

Connector plug M 12

11/03

1 NO / 4 NC with connector plug

11/12

2 NO / 3 NC with connector plug

12/03

1 NO / 5 NC

12/11

2 NO / 3 NC with connector plug

12/12

2 NO / 4 NC

Latching force 5 N

R

Latching force 30 N

Power to unlock

A

Power to lock

Lateral manual release

ED

Manual release on the cover side 

EU

Manual release on the rear side

T

Lateral emergency exit

TD

Emergency exit on the cover side

TU

Emergency exit on the rear side

N

Emergency release

024

U

s

 24 VAC/DC

110/230

U

s

 110/230 VAC

Without LED

G

With LED

Only if the information described in this operating instructions 
manual are realised correctly, the safety function and therefore 
the compliance with the Machinery Directive is maintained.

2.2  Special versions

For special versions, which are not listed in the order code below 2.1, 
these specifications apply accordingly, provided that they correspond to 
the standard version.

2.3  Destination and use

The solenoid interlock has been designed to prevent in conjunction 
with the control part of a machine, movable safety guards from being 
opened before hazardous conditions have been eliminated.

Interlocks with the power to lock principle may only be used 
in special cases after a thorough evaluation of the accident 
risk, since the guarding device can immediately be opened 
on failure of the electrical power supply or when the main 
switch is opened.

The safety switchgears are classified according to 
ISO 14119 as type 2 interlocking devices. 

Manual release

(for set-up, maintenance, etc.)
The manual release is realised by turning the triangular key (M5 
triangular key available as accessory), so that the locking bolt is pulled 
into the unlocking position. Please ensure that jamming by external 
influence on the actuator is avoided. The normal locking function is only 
restored after the triangular key has been returned to its original posi-
tion. After being put into operation, the manual release must be secured 
by installing the plastic cover, which is included in delivery. 

Lateral manual release

Manual release on the cover side 
or on the rear side

(ordering suffix -ED/-EU)

Triangular key TK-M5 (101100887) available as accessory.

Emergency release (ordering suffix -N)

(Mounting and actuation only outside of the safety guard)

The emergency release should only be used in an emergency.
The solenoid interlock should be installed and/or protected so 
that an inadvertent opening of the interlock by an emergency 
release can be prevented.
The emergency release must be clearly labelled that it should 
only be used in an emergency. The label can be used that 
was included in the delivery.

To activate the emergency release in case of an emergency, the orange 
lever must be turned to the stop in the direction marked by the arrow. 
In this position, the safety guard can be opened. The lever is latched 
and cannot be returned to its original position. To cancel the blocking 
condition, the central mounting screw must be loosened to such extent 
that the lever can be turned back into its original position. The screw 
must then be re-tightened.

Emergency exit 

(Fitting and actuation only from within the hazardous area)
To activate the emergency exit of the T version in case of an emergency, 
the orange lever must be turned to the stop in direction marked by the ar-
row. The emergency exit function of the TD and TU versions is activated 
by pressing the red pushbutton. In this position, the safety guard can be 
opened. The blocking condition is cancelled by turning the lever in op-
posite direction or by pulling back the pushbutton. In unlocked position, 
the safety guard is protected against unintentional closing.

Lateral emergency exit

(ordering suffix -T)

Emergency exit on the cover side 
or on the rear side

(ordering suffix -TD/-TU)

Summary of Contents for AZM 161 Series

Page 1: ...for the applications authorised by the manufac turer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instruc tions manual the country specific installation standards as well as all prevailing safety regulations and accident prevention rules Furthe...

Page 2: ...in switch is opened The safety switchgears are classified according to ISO 14119 as type 2 interlocking devices Manual release for set up maintenance etc The manual release is realised by turning the triangular key M5 triangular key available as accessory so that the locking bolt is pulled into the unlocking position Please ensure that jamming by external influence on the actuator is avoided The n...

Page 3: ... voltage Us 24 VAC DC 110 230 VAC Magnet 100 ED Power consumption max 10 W Max fuse rating 6 A gG D fuse Required rated short circuit current 1000 A Use Type 4X Indoor Use and 12 connector fittings Tightening torque rating 4 4 lb in 2 5 Safety classification Standards ISO 13849 1 Envisaged structure Basically applicable up to Cat 1 PL c With 2 channel usage and fault exclusion mechanism applicable...

Page 4: ... 72 52 13 21 41 42 22 14 A2 A1 71 51 63 64 72 52 A2 11 21 41 42 22 12 Q Q A1 71 51 63 64 72 52 11 21 41 42 22 12 A2 P Q AZM 161SK 12 03 AZM 161CC 12 03 A1 71 51 63 64 72 52 13 21 41 42 22 14 A2 Key A Positive break NC contact Monitoring the interlock according to ISO 14119 P Actuated Q Not actuated AZM 161ST with connector AZM 161ST 12 11 AZM 161ST 11 12 A1 A2 41 42 51 52 63 64 13 14 21 22 71 72 1...

Page 5: ... previously checked and met 1 Fitting of the solenoid interlock and the actuator 2 Check the integrity of the cable entry and connections 3 Check the switch enclosure for damage 5 2 Maintenance A regular visual inspection and functional test including the following steps is recommended 1 Check for tight installation of the actuator and the switch 2 Remove particles of dust and soiling 3 Check cabl...

Page 6: ... Wuppertal The currently valid declaration of conformity can be downloaded from the internet at www schmersal net 7 EU Declaration of conformity K A Schmersal GmbH Co KG Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com Place and date of issue Wuppertal February 1 2016 ...