3
AZM 161..-24
AZM 161..-33
Operating instructions
Solenoid interlock
EN
2.4 Technical data
Standards:
IEC/EN 60947-5-1; EN ISO 13849-1;
EN 1088; BG-GS-ET-19
Enclosure:
glass-fibre reinforced thermoplastic,
self-extinguishing
Actuator and locking bolt:
stainless steel 1.4301
Contact material:
Silver
Protection class:
IP 67
Contact types:
change-over contact with double break,
type Zb, with galvanically separated
contact bridges
Switching system:
A
to IEC 60947-5-1; slow action, posi-
tive break NC contact
Positive break travel (unlocked): 9.5 mm
Positive break force (unlocked): each NC contact 10 N
Termination:
Screw terminals or cage clamps or
connector
Cable type:
flexible
Cable section:
min. 0.75 mm², max. 1.5 mm²
(incl. conductor ferrules)
Cable entry:
4 x M16 x 1.5
F
max
:
2000 N
Latching force:
30 N for ordering suffix R
Actuating speed:
max. 2 m/s
Actuating frequency:
max. 1000 operations / h
Mechanical life:
> 1 million operations
Ambient temperature:
– 25 ºC … + 60 °C
Electrical data:
Utilisation category:
AC-15, DC-13
I
e
/U
e
:
4 A / 230 VAC; 2,5 A / 24 VDC; M12
connector, 4 pole: 4 A / 230 VAC
U
imp
:
4 kV; with connector, 4 pole: 2.5 kV
U
i
:
250 V; with connector, 4 pole: 250 V
I
the
:
6 A; with connector 4 pole: 6 A
U
s
:
24 VAC / DC; 110 / 230 VAC
Magnet:
100 % ED
Power consumption:
max. 10 W
Max. fuse rating:
6 A gG D-fuse
2.5
Safety classification
Standards:
EN ISO 13849-1
B
10d
(NC contact):
2,000,000
Service life:
20 years
MTTF
B
d x
x
h
s/h
3600
d
10d
op
op
op
n
0,1 x n
op
t
cycle
(Specifications can vary depending on the application-specific parame-
ters h
op
, d
op
and t
cycle
as well as the load.)
3 Mounting
3.1 General mounting instructions
Three mounting holes are provided for fixing the enclosure. The sole-
noid interlock is double insulated. The use of a protective ground wire
therefore is not authorised. The solenoid interlock must not be used as
an end stop. Any mounting position, provided that the ingress of dirt and
soiling in the used opening is avoided. Unused actuator openings must
be sealed with slot sealing plugs.
Please observe the remarks of the standards EN ISO 12100,
EN 953 and EN 1088.
3.2 Dimensions
All measurements in mm.
30
90
25
130
26
30
18
8
6
6
6
6
8
22,5
20
32
72
26
104
28
4 Electrical connection
4.1 General information for electrical connection
The electrical connection may only be carried out by autho-
rised personnel in a de-energised condition.
At least one magnetic contact with positive break
A
must be
integrated in the safety circuit.
For the cable entry, suitable cable glands with an appropriate degree
of protection must be used. The thin walls of the mounting holes are
removed when the cable gland is screwed in.
4.2 Contact variants
Contacts are shown in the de-energised condition and with the actuator
inserted.
Power to unlock
Power to lock
A1 A2
31 32 41 42 51 52 63 64
13 14 21 22
A2
A1
51 63
52 64
14
22
13
21
32
42
31
41
31
41
13
21
51 63
32
42
14
22
52 64
A2
A1
A1 A2
31 32 41 42 51 52 63 64
13 14 21 22