9 • Schlage • PIM400-485 user guide
PIM400-485 to ACP connection
Review
Components
on page 4 and page 5 before connecting the PIM400-485 to
an Access Control Panel.
CAUTION: Disconnect the Access Control Panel power and batteries before wiring the
PIM400-485 to the panel.
WARNING: Because every Access Control Panel is different, always check the panel’s
instruction manual for appropriate interface wiring.
The EIA RS485 specification labels the data wires as “A” and “B”, however, many RS485
products label their wires “+” and “-”. Some products associate the “+” signal with “A”,
some with “B”. Reversing polarity will not damage either RS485 device, it will just not
communicate; if it does not work, switch the connections.
•
The wires from the Access Control Panel must be a shielded twisted pair. For maximum
wire lengths and cable specifications, refer to
Cable/wire specifications
on page 8.
•
For compliance with UL294 or ULC S319, product must be used with a UL 294 or
ULC S319 Listed Access Control Panel or unit, respectively.
•
Must be used with a UL294 or ULC S318/ULC S319 Listed power-limited Power Supply
capable of sourcing at least 250mA @ 12 or 24 VDC.
ACCESS CONTROL PANEL CONNECTIONS
PIM400-485
connector
PIM400-485
signal
Access control
panel signal
Description
Power (J2)
+
12 or 24 VDC
PIM400-485 inputs for 12 or 24 VDC power.
Draws 250mA max.
If the Access Control Panel (ACP) reader
power outputs do not source enough
current for the PIM400-485, use the ACP
main regulated 12 VDC power supply or
a separate UL294 or ULCS318/ULCS319
Listed 12 or 24 VDC power-limited power
supply.
Power input is non polarized.
–
DC Ground
RS485 (P5)
RDA –
– Receive Data 4-Wire or 2-Wire bi-directional RS485
communication port for interface to Access
Control Panels.
2-Wire installation: Both 2|4 wire jumpers
should be added.
4 -Wire installation: Both 2|4 wire jumpers
should be removed.
Refer to
Typical PIM400-485 to ACP wiring
diagrams
on page 10 and page 11.
TDA –
– Transmit Data
RDB +
+ Receive Data
TDB +
+ Transmit Data
GND
Signal Ground