Schlage PIM400-485 User Manual Download Page 1

*24303034*

24303034

PIM400-485 USER GUIDE

User guide for the panel interface module PIM400-485

Version 2

Version 1

(Manufacturing discontinued)

Para el idioma español, navegue hacia www.allegion.com/us

Pour la portion française, veuillez consulter le site www.allegion.com/us

Summary of Contents for PIM400-485

Page 1: ... GUIDE User guide for the panel interface module PIM400 485 Version 2 Version 1 Manufacturing discontinued Para el idioma español navegue hacia www allegion com us Pour la portion française veuillez consulter le site www allegion com us ...

Page 2: ...ith FCC and Industry Canada RF radiation exposure limits for general population the antenna s used for this transmitter must be installed such that a minimum separation distance of 20cm is maintained between the radiator antenna and all persons at all times and must not be co located or operating in conjunction with any other antenna or transmitter This product is compliant of UL 294 and ULC S319 ...

Page 3: ...he WAPM s using Radio Frequency RF The WAPM is installed at the access point where access will be controlled and or monitored The PIM400 485 enclosure is NEMA Type 4 Getting started The following is an overview of the steps required to set up the PIM400 485 1 Install the WAPM AD 400 WPR400 etc See the installation guide that came with the WAPM or visit www allegion com us see Support Schlage Elect...

Page 4: ...is assigned an even number Tamper status Tamper Status is indicated by the power tamper LED When the cover is off tamper is detected and the power tamper LED will flash green When the cover is on tamper is not detected and the power tamper LED will illuminate steady green Reset Reset is performed by the reset button Press the reset button if the PIM400 485 does not seem to work properly Components...

Page 5: ...shed by walls distance metal objects or barriers Consider the following when placing the PIM400 485 Mount the PIM400 485 within 200 horizontal feet 61 meters of each WAPM with typical building construction When clear line of sight is available communication may be possible up to 1000 feet 305 meters Do not mount the WAPM s and the PIM400 485 on different floors The signal may be degraded and funct...

Page 6: ...e pre installation test on any additional WAPMs If all linking is successful follow steps to wire and mount the PIM400 485 and any additional WAPMs see Drill holes for wiring on page 6 If linking is unsuccessful move the PIM400 485 six to ten inches 15 2 to 25 4 cm in any convenient direction until all WAPMs link successfully If still not successful move the PIM400 485 closer to the WAPMs and repe...

Page 7: ...le locations on the wall with a pencil using the PIM400 485 enclosure as a template L L Be sure to mount the PIM400 485 vertically refer to diagrams on page 6 PIM400 485 version 2 PIM400 485 version 1 Mounting holes Mounting holes 3 Remove the PIM400 485 from the wall and drill the four holes Z zn diameter drill bit recommended L L If the wall does not adequately support the PIM400 485 wall anchor...

Page 8: ... 1 Disconnect all electrical connections to the PIM400 485 version 1 PCBA 2 Remove the four screws from the PIM400 485 version 1 PCBA Set aside two 2 of the screws for later use 3 Remove the PIM400 485 version 1 PCBA from the enclosure 4 Drill a Z x 25 mm wire routing hole in the bottom of the PIM400 485 version 2 as shown below 5 Place the PIM400 485 version 2 into the PIM400 485 version 1 enclos...

Page 9: ...4 or ULCS319 product must be used with a UL 294 or ULCS319 Listed Access Control Panel or unit respectively Must be used with a UL294 or ULCS318 ULC S319 Listed power limited Power Supply capable of sourcing at least 250mA 12 or 24 VDC ACCESS CONTROL PANEL CONNECTIONS PIM400 485 connector PIM400 485 signal Access control panel signal Description Power J2 12 or 24 VDC PIM400 485 inputs for 12 or 24...

Page 10: ...WIRE RDA TDA RDB TDB GND AUXTAMPER ATTENTION ELECTROSTATIC SENSITIVE DEVICE POWER TAMPER PIM400 485 RS485 P5 P5 USB Install Jumpers Power Supply UL294 or ULCS318 ULCS319 Listed power limited 250mA 12 or 24 V DC 2 Wire 4 Wire Access Control Panel Shield Access Control Panel Shield Power Supply UL294 or ULCS318 ULCS319 Listed power limited 250mA 12 or 24 V DC Remove Jumpers 18 AWG 1000 feet max run ...

Page 11: ...ly UL294 or ULCS318 ULCS319 Listed power limited 250mA 12 or 24 V DC 2 Wire 4 Wire Access Control Panel Shield Shield 18 AWG 1000 feet max run length 18 AWG 1000 feet max run length Remove Jumpers Install Jumpers Access Control Panel Power Supply UL294 or ULCS318 ULCS319 Listed power limited 250mA 12 or 24 V DC PIM400 485 Version 1 ...

Page 12: ... REM I O 6dB NEMA 4 Indoor Outdoor Optional remote directional antenna 6 dB gain Link mode The PIM400 485 can be placed into link mode using the Schlage utility software SUS on the handheld device HHD Refer to the Schlage utility software user guide for information The PIM400 485 can also be placed into Link Mode directly through select Access Control Panels Schlage Utility Software SUS The Schlag...

Page 13: ...tween the PIM400 485 and the Access Control Panel may be damaged Replace the RS485 cable between the PIM400 485 and the Access Control Panel The RS485 signals between the PIM400 485 and the Access Control Panel may be wired incorrectly Refer to PIM400 485 to ACP connection on page 9 or ACP system documentation for proper wiring instructions The RS485 address of the PIM400 485 may not match the RS4...

Page 14: ...l Refer to Wire routing on page 8 for proper wire routing instructions The PIM400 485 does not communicate with Wireless Access Point Modules WAPMs The Antenna Module may not be properly installed Ensure that the Antenna Module is installed and properly seated Wiring may cause interference with the internal antenna on the Antenna Module Check to ensure that wiring is properly routed in the PIM400 ...

Page 15: ...requency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communication However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try...

Page 16: ...s having a gain greater than the antenna type approved in the list are strictly prohibited for use with this device However antennas of the same type with a gain equal to or less may be used Examples of this may include a directional panel antenna with a gain equal to or less than 8 5 dBi may be used with this module an omni directional antenna with a gain equal to or less than 2 0 dBi may be used...