Schlage 900-FA Installation Instructions Download Page 2

© Allegion 2014

Printed in U.S.A.

44487072 Rev. 01/14-b

b  If installing to PS902 main board

Remove Jumper

Install 900-FA Here

Note:

  Complete power failure shall result in a fail safe operation.

 

When connected to a fire alarm releasing control unit, total  

 

 

loss of power for the locking mechanisms shall be configured 

 

for a fail safe operation. 

   900-FA wiring

NC

FA2

FA1

NO

C

One 900-FA Board - Automatic Reset

Two 900-FA Boards on one power supply
Automatic Reset

NC

FA2

FA1

NO

C

NC

FA2

FA1

NO

C

NC

FA2

FA1

NO

C

One 900-FA Board - Manual Reset

Two 900-FA Boards on two power supplies
Automatic Reset

NC

FA2

FA1

NO

C

NC

FA2

FA1

NO

C

Supervision Output

Contacts Shown FA Active (open)

Fire Alarm Input

NC

C

NO FA1 FA2

Terminal Definitions

Fire Alarm Contact

Closed = no fire

Open = fire

                  

Manual Reset     

(Temporarily close to reset)

Fire Alarm Contact

Closed = no fire

Open = fire

Fire Alarm Contact

Closed = no fire

Open = fire

Fire Alarm Contact

Closed = no fire

Open = fire

Note:

  Use 18 gauge wire for all wiring. Wire 

 

length dependent on physical layout. 

NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS OR KEYLOCK