Schischek InMax-50.75 Quick Start Manual Download Page 3

E X P L O S I O N P R O O F

InMax- 50.75  ►

InMax- 100 

 

InMax- 150 

 

InMax-  30 -F  ►

InMax-  50 -F  ►

InMax-  60 -F  ►

50 Nm

100 Nm

150 Nm

30 Nm

50 Nm

60 Nm

 ▼

75 Nm

 ▼

 40 s/90° 

  60  s/90° 

 

90  s/90°

 

  120  s/90° 

  150  s/90° 

00

01

02

03

04

05

06

07

08

09

InBox

a

a

a

b

b

b

+

~

+

~

+

~

+

~

~

~

~

~

PE

PE

PE

PE

1

1

1

1

2

2

2

2

3

3

3

3

4

4

4

4

PA

PA

PA

PA

1

4

2 3

5 6

< 5°

> 85°

 

 

U < 90 V AC/DC  2 AT  10 AT

U > 90 V AC/DC  5 AT  10 AT

S

T

www.schischek.com

Schischek GmbH

 Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

InMax-M-3P_en

V04 –  31-Oct-2018

InMax-... 

InMax-...-F 

InMax-...-S   InMax-...-SF

Special option 

... -CTM 

  ... -VAM

Electrical connection

Parameters, adjustments and failure indication

Parameter selection

Functions, adjustments and parameters

Type

Running times

Position of switch (S)

Torques

Example: 

InMax-50.75

Requested parameter: 

Torque 

75 Nm

Motor running time  90 s/90°

Result:

Switch position  

07

All actuators are equipped with a universal supply unit working at a voltage range from 

24...240 VAC/DC. The supply unit is self adjusting to the connected voltage! 

The safety operation of the spring return function works if the supply voltage is cut. 

For electrical connection a terminal box is required (e.g. InBox). 

An over-current protection fuse < 10 A has to be provided by installer. 

Note: the initial current is appr. 2 A for 1 second.

Integrated auxiliary switches signal the rotation angle’s position. U

min

 and I

min

 change once 

the switches were operated with higher voltage or current.

Installation

Supply * 

24...240 VAC/DC ± 10 %

* electrical wiring see diagrams

On-off / 3-pos. 

SB 2.2

On-off / 3-pos. 

SB 1.0

On-off  (1 wire) 

SB 2.3

Wiring of integrated auxiliary switches 

SB 3.0

Wiring diagram   InMax- ...  (without spring return)

Wiring diagram   InMax- ... -F  (with spring return)

Wiring diagram   InMax- ... -S and ... -SF

Attention!

At 1-wire control 

mode the heater 

does not work in 

case of open contact. 

Wiring of actuator acc. to type and 

application see diagrams above

Wiring of the integrated, potential free 

auxiliary switches

24...240 VAC/DC

24...240 VAC/DC

24...240 VAC/DC

24...240 VAC/DC

Attention

During commissioning apply 

a self adjustment drive. 

Regard duty cycle at 

motor running times!

Never use spring return 

actuators without external load.

Auxiliary switches * 

see Technical data

Integrated auxiliary switches, 

Grid fuse-protection recommended. 

 

min. max.

A)  Self adjustment of angle of rotation 

Turn switch (S) to position 02 (low torque) or 07 (high torque). Press button (T) for 

a minimum of 3 seconds. The actuator drives to both end positions and detects the 

blocking positions. The LED flashes GREEN during adjustment. 

The adjustment takes about 180 seconds (90 sec. “On”, 90 sec. “Off”).

B)  Selecting motor running time and torque 

Adjust parameters only if actuator is in idle state or without applied potential. 

Turn switch (S) to the position required for the intended operation acc. to table 

above. The selected parameters will be carried out at the actuator’s next operation.  

C)  Additional information for control in 3-pos. operation 

a closed, b open   = direction I  

a and b closed  

= motor doesn’t work 

b closed, a open   = direction II  

a and b open  

= motor doesn’t work 

The rotation direction (I and II) depends on left/right mounting of the actuator to the 

damper. To reverse the rotation direction (by motor) exchange the electrical wiring 

of terminal 3 and 4.

▪  Do not open the cover when circuits are live

▪  Connect potential earth

▪  Close all openings to ensure enclosure protection

▪  Clean only with damp cloth, avoid dust accumulation

Switch – Push button – Lamp 

for adjustment 

(behind the blanking plug)

10-position switch (S)

3-colour LED

Push button (T)

3 / 4

Summary of Contents for InMax-50.75

Page 1: ...me 20 s 90 On off and 3 pos control with or without spring return function 30 50 60 75 100 150 Nm actuators in the same housing size 100 overload protected Compact design and small dimension L W H 288 149 116 mm Direct coupling to the damper shaft with double square connection 16 16 mm 95 angle of rotation inclusive 5 pretension Robust aluminium housing optional with seawater resistant coating or ...

Page 2: ... DC 48 V 1 A Imin AC DC 5 mA Imin AC DC 100 mA Axle of the actuator Double square 16 16 mm direct coupling 100 overload protected Electrical connection Cable 1 m wire cross section 0 5 mm equipotential bonding 4 mm Connections require a terminal box Diameter of cable Ø 7 1 mm Ø 7 1 mm Ø 7 1 mm Ø 7 4 mm Ø 7 4 mm Ø 7 4 mm 2 cables in the versions S and SF Ø 7 4 mm Cable gland M16 1 5 mm Manual overr...

Page 3: ...ing return Wiring diagram InMax F with spring return Wiring diagram InMax S and SF Attention At 1 wire control mode the heater does not work in case of open contact Wiring of actuator acc to type and application see diagrams above Wiring of the integrated potential free auxiliary switches 24 240 VAC DC 24 240 VAC DC 24 240 VAC DC 24 240 VAC DC Attention During commissioning apply a self adjustment...

Page 4: ...ection of running time Actuators are equipped with a direct coupling double square shaft connection of 16 16 mm The housing of the actuator is axially symmetrically built to select Open close direction of the spring return function by left right mounting Using the 10 position switch different motor running times and spring return running times can be selected on site in acc to the actuator type D ...