background image

Schischek GmbH 

Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn,  Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

www.schischek.com

E X P L O S I O N P R O O F

Description

The 

InBin-P-100

 pressure switch generation from 5...100 Pa is a revolution 

for differential pressure switches  in HVAC systems, in chemical, pharma-
ceutical, industrial and Offshore-/Onshore plants. 
IP66 protection, small dimension, universal functions and technical data 
guarantee safe operation even under difficult environmental conditions. 
The switching point is scalable within the maximum ranges. The integrated 
display is for actual value indication which can be switched off.
All sensors are programmable on site without any additional tools.

InBin-P-100-OCT

 is equipped with stainless steel 316L tubing Ø 6 mm. 

Application

Highlights

Type 

Sensor  

Supply 

Range 

Min. setting 

Max. pressure 

Output switch 

Max. ratings 

Wiring diagram

InBin - P-100 

Pressure 24 

VAC/DC  0...100 Pa 

     5 Pa 

    5.000 Pa 

pot. free contact 

250 VAC, 0,1 A / 30 V, 0,5 A    SB 1.0

InBin - P-100 - CT 

as above with aluminium housing and Amercoat painting (sensor connection and cable glands nickel-plated, screws in stainless steel)

InBin - P-100 - OCT 

as above offshore version seawater-resistant, with aluminium housing and Amercoat painting (stainless steel tubes for clamping ring connection, 

 

cable glands M20 × 1,5 mm nickel-plated, screws in stainless steel)

Electrical, binary pressure or differential pressure switches 

with adjustable switch activation delay

24 VAC/DC supply voltage, output potential free switching contact  

 For industrial use 

 Integrated junction box

 Power supply 24 VAC/DC

 Output potential free switching contact

 Display with backlight, can be switched off

 Adjustable switching characteristics

 Adjustable hysteresis

 Adjustable starting bypass time 

 Adjustable switch activation delay

 Compact design and small dimension  (L × B × H = 180 × 107 × 66 mm) 

 Robust aluminium housing in protection class IP66

 Down  to 

20°C ambient temperature applicable

 Password  locking

 CT versions have an excellent resistance to chemicals and seawater

 OCT as CT version plus pressure tube connection for clamping ring Ø 6 mm

InBin-P

  Pressure switches from 5 Pa...100 Pa

1 / 6

Compact. Easy installation. Universal. Cost effective. Safe.

InBin - P-100

InBin - P-100 - CT

InBin - P-100 - OCT

Subject to change!

Offshore version ...-OCT

Pressure or ∆ pressure switch

Amercoat version ...-CT

D.IB-P100-02.01-en

23-Aug-2012

Summary of Contents for InBin-P-100

Page 1: ...connection and cable glands nickel plated screws in stainless steel InBin P 100 OCT as above offshore version seawater resistant with aluminium housing and Amercoat painting stainless steel tubes for clamping ring connection cable glands M20 1 5 mm nickel plated screws in stainless steel Electrical binary pressure or differential pressure switches with adjustable switch activation delay 24 VAC DC ...

Page 2: ...uttons for configuration Housing protection IP66 in acc to IEC 60529 Housing material Aluminium casting coated CT OCT version in Amercoat marine painting seawater resistant OCT Offshore version Dimension weight L W H 180 107 66 mm 950 g Ambient temperature humidity 20 50 C 0 95 rH non condensed Storage temperature 40 70 C Measuring range 0 100 Pa Range scalable on site Minimum measuring range is 5...

Page 3: ...ration A Installation commissioning maintenance The cable has to be drawn through the cable gland After electrical connection the cable gland must be fixed tighten IP66 must be fulfilled In acc with operation InBin switches are maintenance free The sensors must not be opened by the customer For electrical connection use the internal junction box Attention Before opening the internal junction box c...

Page 4: ...steresis select physical unit adjust hysteresis Pa mBar InH2O Menu 6 mode select switching charateristic norm open no norm closed nc Menu 7 Menu 8 Menu 9 Menu 10 Menu 11 Menu 12 Menü 13 Menu 16 Menu 15 lamp select backlight save select save data security select password adjust set 1 select normal sensor interval no yes return default setting on off enter password Menu 14 Menu 1 Preset select appli...

Page 5: ...set To beware complexity during the parametrisation process the InBin P has several predefined setups which distinguish between its intended application You ll find a detailed desciption of all possible presets in the following section Fan speed monitoring The preset FAN is designed for use in fan speed monitoring applications state output switch 1 normal state output switch 2 optional setpoint 1 ...

Page 6: ...t 2 Mid range the normal range is between setpoint 1 and setpoint 2 for 2 stage devices only Switching characteristic mid range normally open state output switch 1 normal state output switch 2 optional setpoint 1 normal green green red red setpoint 2 Mid range the normal range is between setpoint 1 and setpoint 2 for 2 stage devices only Switching characteristic down range normally closed state ou...