Page 2 of 6
FCR1 Installation Guide
When Installing Interceptor Inside
SPECIAL PRECAUTIONS
Installation Instructions
Hydrostatic Slabs (or Pressure Slabs)
High Temperature Kitchen Water
concrete slab subject to hydrostatic pressure
watertight
concrete
vault
Interceptor
Interceptor
Interceptor
Do not install this unit in any manner
except as described in these instructions.
Doing so may result in property damage, personal injury or death.
DO NOT AIR TEST UNIT OR RISER SYSTEM!
For Schier Grease Interceptor Installations - Failure to follow this guidance
voids your warranty
If water is entering the interceptor at excessive temperature (over
150º F), a drain water tempering valve (DTV) and approved backflow
prevention assembly must be installed. Most state and local
plumbing codes prohibit water above 150º F being discharged into
the sanitary sewer. Water above 150º F will weaken or deform PVC
Schedule 40 pipe, poly drainage fixtures like interceptors and erode
the coating of cast iron (leading to eventual failure).
Installation instructions and additional
components are included with the
interceptor. Read all instructions prior
to installation. This interceptor is
intended to be installed by a licensed
plumber in conformance with all
local codes.
If your dishwashing sink(s)
discharges into a floor
drain/sink (drain), you
must regulate the flow into
the drain to avoid an
overflow of water onto the
kitchen floor. This can be
done by installing a valve
or flow restriction cap on
the sink piping that
discharges into the drain.
See drawing for guidance. For detailed guidance on indirect
connections, go to:
webtools.schierproducts.com/Technical_Data/Indirect_Connections.pdf
When installed under a
hydrostatic slab (slab
designed to withstand
upward lift, usually
caused by hydrostatic
pressure) interceptor
must be enclosed in a
watertight concrete vault.
ODOR ALERT!
Do not install air
gap on outlet side
of interceptor.
Interceptor
Interceptor
Interceptor
Interceptor
Interceptor
Interceptor
cold water supply line
high temperature e
ffl
uent ( > 150º F)
approved backflow prevention assembly
DTV (drain water tempering valve)
directly connected
indirectly connected
Fernco or similar
rubber flow
restriction end cap
installation
instructions
inside