4.2
Reset of Oil Mist Alarms
CAUTION!
Use a monitoring device at a safe location (e.g. ECR)
to check for the actual oil mist concentration that is
requested by the IACS. In case of an Oil Mist Alarm,
Schaller Automation strongly recommends to
approach the engine only after indicated oil mist
concentration (LED chain) has lowered to half of its
bar indication (VISATRON®-device and Remote
Indicator II).
Follow the instructions of engine builder, ship yard
and ship owner!
In case of a High Oil Mist Alarm the Detector can be
reset if the Oil Mist Concentration has lowered below
the Alarm level.
The alarm condition can be reset only by pressing the Oil-Mist-Alarm RESET button.
Figure 33:
Oil-Mist-Alarm RESET button