background image

4

Novenco Building & Industry A/S

Industrivej 22

Tel. +45 70 77 88 99

4700 Naestved

www.novenco-building.com

Denmark

6.5 Detaching the motor

Before motor detachment, disconnect the 
power supply and motor cable. Next, 
detach the ducts and outlet guide vane (fig. 
8 pos. 13, 10, 11, and 14) on the outlet side.

Remove the impeller centre screw (pos. 09) 
and centre disc (pos. 08).

Detach the impeller using a puller secured 
in the two threaded puller holes in the hub 
boss (pos. 12). 

Loosen the screws in the motor shell (pos. 
05 and 06). The motor (pos. 01) and motor 
flange (pos. 02) can then be detached.

When dismantling the fan, be careful not to 
expose individual parts to impacts or other 
forces that might damage the motor 
bearings or fan parts.

6.6 Fitting the motor

After servicing is complete the motor must 
be refitted. Check that the motor flange (fig. 
8 pos. 02) is correctly positioned and that 
the motor shaft is concentrically positioned 
in the fan housing before tightening the 
bolts (pos. 06).

Refit the impeller (pos. 07) on the motor 
shaft by means of a puller secured in the 
threaded hole on the motor shaft. Tighten 
the impeller hub against the motor shaft 
collar. Check that blade clearance is equal 
around the entire circumference of the 
housing. If this is not the case, adjust the 
motor position in the suspension system.

Now fit the centre screw (pos. 09) and centre 
disc (pos. 08). Replace lock washers and 
lock nuts when reassembling the fan. 
Finally, connect the motor cable in the 
terminal box (pos. 01) and any ducts and 
outlet guide vane (pos. 13). 

To restart the fan, follow the procedure 
described in section 5. Start-up.

6.7 Blade pitch adjustment

The blade pitch is factory set using a special 
tool (fixture) to provide the output required 
by the customer.

If a different output is required, it is possible 
to alter blade pitch. This requires 
knowledge of the motor load and the max. 
permissible blade pitch in relation to the 
motor rating (in case of blade pitch 
increase).

Please contact Novenco before adjustment 
of blade pitch. Special tools for blade pitch 
adjustment and instructions for impeller 
balancing are available from Novenco.

A brochure describing the blade pitch tool 
and its use is available on request.

6.8 Fault finding

Possible operating faults are described in 

the following.

Insufficient output

Blocked air supply on the inlet side.

• Damper closed
• Duct  blocked
• Supply fan, if any, stopped
• Motor  defective
• Motor cut out
• Incorrect direction of impeller rotation 

Noise/vibration

• Bearings in electric motor defective
• Impeller out of balance
• Impeller worn/damaged
• Bolts/components loose
• Impeller blades have different pitch
• Fan operating in "stall" mode – this 

may damage the system and should be 
remedied immediately, see 
"Insufficient output".

7. Testing functionality and 

operational readiness

To maintain their fire approval, ACP and 
ACG Smoke fans must be tested every three 
months with respect to functionality and 
operational readiness.

If ACP and ACG Smoke fans are also used 
for ventilation purposes, such tests need 
only be performed at six-month intervals 
provided the fan is started at least once a 
day by means of a time switch or carbon 
monoxide sensor. 

7.1 Periodic inspection

NovAx smoke fans must always be 
maintained in proper operating condition. 
To ensure satisfactory operation and long 
service life, the fans should be inspected 
every six months. 

Such inspection should include the 
following. 

• Measurement of power consumption
• Measurement of fan housing vibration
• Control of fixation bolt torque and, if 

necessary, readjustment

• Visual inspection of impeller, housing 

and wiring

• Cleaning

– Use compressed air to clean the 

inside

– Use water to clean the outside

It is recommended that a log be kept of all 
values and observations. 

8. Sound

The sound generated by the fans depends 
on installation and operating conditions, 
and general data on sound generation is 
therefore unavailable.

Please refer to the NovAx catalogue 
material and the AirBox program for 
calculation of specific sound emissions.

9. Declaration of conformity

Novenco Building & Industry A/S
Industrivej 22
4700 Naestved
Denmark

hereby declares that Novenco axial flow fan 
types ACP Smoke 400-1600 and ACG 
Smoke 400-1600 have been manufactured 
in accordance to the below directives of the 
European Council and that they comply 
with the below standards and regulations.

Directives

– Machinery 2006/42/EU
– ECO design 2009/125/EU and regula-

tion 2017/1369/EU

– EMC 2014/30/EU
– LVD 2014/35/EU

Applied standards and regulations

– ANSI/AMCA 300-14
– EU regulation 327/2011
– DS/EN 1037 + A1:2008
– DS/EN ISO 1461:2009
– DS/EN 1886:2008
– DS/ISO 2954:2012
– DS/EN ISO 5801:2017
– DS/EN ISO 9001:2015
– EN ISO 12100:2011
– DS/EN 12101-3:2015
– DS/EN ISO 12499:2009
– DS/EN ISO 12944-2:2017
– ISO 13348:2007, class AN3
– DS/EN ISO 13857:2008
– DS/EN ISO 14001:2015
– DS/ISO/TR 14121-2:2012
– ISO 14694:2003
– DS/EN 16798-3:2017
– DS/ISO 21940-11:2016
– DS/ISO 21940-14:2012
– DS/EN 60204-1:2006 + A1:2009
– DS/EN 61000-6-1:2007
– DS/EN 61000-6-2:2005
– DS/EN 61000-6-3:2007 + A1:2011
– DS/EN 61000-6-4:2007 + A1:2011
– DS/EN 61800-3:2005, class C2 + 

A1:2012

It is a condition that Novenco installation 
instructions have been followed.

Naestved, 1.08.2020

Peter Holt
Technical director
Novenco Building & Industry A/S

Reviews: