7. Inspection and test

It is recommended to test and inspect the 
NovAx ACN-ARN fans at regular inter-
vals with regard to operability and oper-
ating conditions.

Fans approved for smoke control must 
be tested and inspected four times a year.

Smoke exhaust fans that double as fans 
for standard ventilation, must be tested 
every six months, if these are started at 
least once a day - for example as a result 
of connection to a time switch or carbon 
monoxide alarm.

Extent of inspection

• Measure power consumption
• Measure vibrations on fan casing
• Check torques for fixing bolts and 

correct if necessary

• Visual inspection of rotor, fan 

casing and electric connection

• Cleaning

– inside with pressure air
– outside with water

It is recommended to enter all values and 
observations in a log.

8. Sound

The sound generation of the fans de-
pends on installation and operating con-
ditions, which means that no general 
sound generation data can be given.
Refer to the product catalogue, Novenco 
AirBox computer program and the tech-
nical fan specifications.

9. Safety

The NovAx axial flow fans must be in-
stalled according to Novenco’s, the cur-
rent and local safety regulations. At a 
minimum these include EN 13850.
It is recommended to review and revise 
safety procedures regularly.

Safety check

• Test if safety procedures and the 

installation work correctly.

• Check if safety regulations have 

been changed and if the installation 
needs revising.

• Consider additional measures to 

improve the safety of the 
installation. For example, by 
mounting wire guards on inlet and 
outlet.

10. Spare parts

Contact Novenco for information about 
and ordering of spare parts.

11. Patents and trademarks

Novenco

®

 , 

 and 

 are 

registered trademarks of Novenco A/S 
or Novenco Marine & Offshore A/S.
AirBox™ and NovAx™ are trademarks 
of Novenco Building & Industry A/S.

Other trademarks appearing in this doc-
ument are the property of their respec-
tive owners.

Copyright (c) 1985 - 2018,
Novenco Building & Industry A/S
All rights are reserved.

12. Quality management

Novenco Building & Industry A/S is ISO 
9001 certified. This means that all fans 
are inspected and tested, before leaving 
the production.

13. Warranty

Novenco provides according to law a 
standard 12 months warranty from the 
product is sent from the factory. The war-
ranty covers materials and manufactur-
ing defects. Wear parts are not covered.
Extended warranty can be agreed upon.

14. Declaration of conformity

The Machinery Directive 2006/42/EU, 
part 2, A 

Novenco Building & Industry A/S
Industrivej 22
4700 Naestved
Denmark

hereby declares that axial flow fans type 
ACN smoke 400-1600 and ARN smoke 
900-1600 have been manufactured in 
conformity with the Council's directives 
2006/42/EU regarding mutual approxi-
mation of the machinery laws of the 
member states.

Directives

• Machinery 2006/42/EU
• ECO design 2009/125/EU
• ECO energy labelling 2010/30/EU
• EMC 2014/30/EU
• LVD 2014/35/EU

Applied standards

EU 327/2011:

Fans driven by motors with electric 
power between 125 W and 500 kW

EN ISO 12100:2011:

Safety of machinery
- General principles for design
- Risk assessment and risk reduction

EN 12101-3:

Smoke and heat control systems - Part 
3, class 1

EN ISO 13857:

Safety of machinery - Safety distances

EN 60204-1:

Safety of machinery - Electrical equip-
ment of machines Part 1: General Re-
quirements

EN 61000-6-2:

EMC - Part 6-2: Generic standards - 
Immunity for industrial environ-
ments

EN 61000-6-3:

EMC - Part 6-3: Generic standards - 
Emission standard for residential, 
commercial and light-industrial envi-
ronments

EN 61800-3, class C2:

Adjustable speed electrical power 
drive systems, EMC requirements 
and specific test methods

It is conditioned that Novenco Building 
& Industry A/S' instructions for installa-
tion and maintenance have been fol-
lowed.

Naestved, 01.05.2018

Peter Holt
Technical director
Novenco Building & Industry A/S

Summary of Contents for NOVENCO NovAx ACN SMOKE

Page 1: ...Pure competence in air 918149 0 ACN ARN SMOKE INSTALLATION AND MAINTENANCE ENGLISH ...

Page 2: ...pplied with approval num ber class or category are also mentioned as well as test standard applied EN 12101 3 Fan pressure air quantity out put and maximum speed per minute are also on the fan nameplates The fan is also provided with a motor nameplate with relevant motor data in cluding insulation class of the motor 2 2 Weight The total weights shown in table 1 apply to axial flow fans type ACN AR...

Page 3: ...n is provided with an arrow plate denoting the direction of airflow through the fan casing See during instal lation that the fan is oriented so as to pro vide the desired direction of airflow in the system The best way of installing the fan is with asupportframe optionalaccessory but it may also be suspended in the fan cas ing flanges or in special carriers The carriers must not hamper the free in...

Page 4: ...fig 6 The duct or inlet cone on the fan inlet side must be designed to ensure smooth and undisturbed airflow ACN ARN smokefansarepreparedforcircularduct connection on both inlet and outlet sides Flanges supplied as standard for type ACN ARN comply with Eurovent 1 2 Systems with higher vibration levels or more exacting performance require ments must be provided with expansion joints between fan and...

Page 5: ... 7 mm s RMS measured radially at 2 points 90º offset and at the free shaft end of the motor Otherwise the fan must be balanced Operation at vibration levels exceeding 11 mm s RMS is not allowed for fixed fan positions Operation at vibration levels exceeding 18 mm s RMS is not allowed for fans on support frames or anti vibration dampers ISO 2954 Requirements for instruments for measuring vibration ...

Page 6: ...an casing must be the same throughout the circumference If neces sary adjust the motor location in the sus pension arrangement Now mount centre screw item 01 cen tre disc item 02 and hub cover item 03 Replace lock washers or lock nuts during fan assembly Finally connect motor cable item 13 in terminal box item 12 and ducts if any To start the fan follow the procedure de scribed in section 5 Start ...

Page 7: ... A S AirBox and NovAx are trademarks of Novenco Building Industry A S Other trademarks appearing in this doc ument are the property of their respec tive owners Copyright c 1985 2018 Novenco Building Industry A S All rights are reserved 12 Quality management NovencoBuilding IndustryA SisISO 9001 certified This means that all fans are inspected and tested before leaving the production 13 Warranty No...