Operating and mounting instructions according to ATEX for
RS-N/RS-M/MWK-OB/MWS-OB/MWK-MB/MWS-MB
Z10/03 - 8
Construction subject to change.
No return possible!
06.02.2018
Version:
Information regarding assembly and commissioning
Prior to being installed in the ventilation system, the silencers
must be checked for damage. Damaged silencers must not be
installed.
The device may only be used in accordance with its designated
use in air ventilation systems for supply air and return air.
Use only approved fastening material for mounting.
No additional parts must be fastened to the silencer.
The silencer must be connected to the ventilation duct network
on both sides in electrically conducting fashion.
In order to avoid the risk static charges, the silencer must be
connected to the potential bonding on the grounding connection
provided for this purpose.
Make sure that the ventilation systems are not subjected to any
anomalous operating conditions, such as vibrations, pressure
surges or high proportions of solids in the medium.
Information regarding maintenance and inspection
Proper maintenance increases operational safety and the serv-
ice life of the device. This is why the devices should be subjected
to regular inspection.
If inspection dates are prescribed by law, they must be complied
with.
The operating personnel must be informed, prior to starting
maintenance and inspection work.
The personal safety measures must be looked up in the safety
data sheet. Hazard caused by contact or inhaling hazardous sub-
stances must be excluded by taking appropriate safety meas-
ures.
Prior to maintenance or inspection, all system components up-
and downstream of the device must be switched off and secured
against being switched on again.
The following inspection criteria must be observed
:
- Visual inspection of the device
- Check the fastening of the device
- Check the grounding connection for tight fit and good contact
- Functional check
- For additional inspections, please refer to the technical docu-
mentation or additional maintenance instructions