Schako DISA-300 Installation, Mounting And Maintenance Download Page 5

Installation, Mounting and Maintenance DISA-300

Z11/23 - 5

Construction subject to change.

No return possible!

20.10.2015

Version:

Installation and commissioning

Operating conditions

Prior to installation or commissioning of the device, the follow-

ing operating conditions must be observed:

Material reception 

Upon reception of the materials, the components must be care-

fully checked, in order to guarantee that no transport damage

has taken place. Moreover, the dimensions, composition and

number of the identification sticker must be checked as to

whether they are as ordered.

Identification sticker:

To prevent possible damage during transport, the devices will

be delivered ex works on pallets (that correspond to the partic-

ular weight and dimensions) wrapped with tapes and transpar-

ent plastic film. It is recommended leaving this protection in

place until the device is commissioned. The openings of the

pipes should be closed with dust caps to avoid dust and entry of

dirt. 

Transport, lifting and handling

Transport and handling of the unit

shall take place in the position in

which the unit is to be built in later

on, unless expressly stated other-

wise on the unit.

Transport, unloading and lifting of

the unit shall take place with the

necessary care and using tools that

are appropriate for the weight and

dimensions.

(1) 

Standard unit: h slot + grille and heat exchanger (empty)

Storage

If the device is not installed immediately after its reception, it

must be stored according to the following instructions:

- Coolant or heating fluid: water or glycols (ethylene

 or propylene) at a concentration below 60%.

- Water inlet temperature: above the dew point up to 80°C

(Please note that some quick-action plugs do not work at

water temperatures above 65°C)

- Air inlet temperature: from 2 to 45°C
- Max. operating pressure: 8 bar / 125°C

-

2:

 Number of supply air slots - 2 supply air slots -

-

H: 

2-pipe system

-

OL: 

Without air deflection blades

-

SR: 

Foldable perforated sheet, - perforation Ø 6 mm -

-

A: 

Nozzle configuration - A -

-

298: 

Width -298 mm-

-

900: 

Nominal length - 900 mm  -

-

1200: 

Total length -1200 mm-

-

M: 

Housing position - centre -

-

WS1:

 Hydraulic connection - left -

-

H: 

Connection - horizontal -

-

AS1

: Number of connection pipes - 1 connection pipe arranged

-

123:

 Diameter of the connection pipes - 123 mm -

-

2E:

 Model with two end pieces

To prevent deposits and corrosion, 

the quality of the water for filling the registers must

comply with regulations VDI 2035 and DIN 50930.

SCHAKO Iberia, S.L. - Pol. Ind. Río Gállego, C/B, nave 3 - E-50840 San Mateo de Gállego.

Model

 / Modelo / Modell

DISA-300/2/H/OL/SR/A/298/900/1200/M/WS1/H/AS1/123/2E

 Order 

nr.

 / Nº Pedido /  Auftragsnr: 

2198/09

 Date 

/ Fecha /Datum: 

22/10/2009

 Reference

 / Referencia / Referenz: 

Sala 1 Hospital Clínico

 Comments 

/ Observaciones / Bemerkungen:

Read manual of instructions

 / Lea el manual de instrucciones / Betriebs- und 

Wartungsvorschriften beachten.

Do not drill the machine

 / Maschine nicht durchbohren / No taladrar la máquina

Special attention in the connection nuts-coil

 / Besondere Vorsicht an der 

Registerverschraubung/ Especial cuidado en la conexión tuercas-batería .

Recycle or arrange the residues according to the current rules

 / Recicle o gestione 

los residuos según la normativa vigente. Bitte, entsprechend der gültigen 
Gezetzgebung recyclen.

NL

900 1200 1500 1800 2100 2400 2700 3000

Weights

 (1) 

(kg) 

13

17

20

24

27

31

34

38

- The device must be stored at a dry, clean, safe location

where no damage to the device can occur, i.e., outside

corrosive atmospheric influences.

- Leave the protections attached ex works (film, tapes, pal-

lets, etc.) on the device, unless they have already been re-

moved beforehand.

- Cover the device with tarpaulins, in order to protect it from

dust, moisture and extreme temperatures.

- Entries, openings and pipes must be hermetically sealed

with dust caps.

Should manufacture-related damage be detected

on the device, please contact your local sales office

prior to installation.

The unit shall only be held in position or moved 

by holding on to the housing. The weight must not

rest on the water connections.

SCHAKO cannot be held liable for damage to the

unit caused by improper handling or handling not

mentioned here, loading or unloading.

Summary of Contents for DISA-300

Page 1: ...Ferdinand Schad KG Steigstraße 25 27 D 78600 Kolbingen Telephone 49 0 74 63 980 0 Fax 49 0 74 63 980 200 info schako de www schako de Installation Mounting and Maintenance DISA 300 ...

Page 2: ...livered model 4 Function 4 Installation and commissioning 5 Operating conditions 5 Material reception 5 Transport lifting and handling 5 Storage 5 Installation 6 Mounting 6 Hydraulic connections 7 Connecting the air ducts 7 Mounting accessories 8 Adjustment of the air deflection blades 8 Checks 8 Maintenance 9 Disassembling the units 9 Air ducts and plenum box 10 Grilles 10 Registers 10 Checking t...

Page 3: ... the return and replacement of defec tive materials Recycling The inspection installation hydraulic connection and commissioning of the device must be carried out by qual ified skilled personnel only in compliance with the current regulations Electric and hydraulic connections and their correct func tioning are the responsibility of the installer Do not change any control or safety elements withou...

Page 4: ...ed sheet grille made of gal vanised sheet steel perforated sheet grille models SR SQ RE and OB made of extruded aluminium profile PA Both painted to RAL 9010 white standard End pieces 4 Sheet steel painted to RAL 9010 Hydraulic connections 5 Upon customer request the hy draulic connection to the registers can be established either on the left hand WS1 or right hand side WS2 of the unit Function Th...

Page 5: ... mm A Nozzle configuration A 298 Width 298 mm 900 Nominal length 900 mm 1200 Total length 1200 mm M Housing position centre WS1 Hydraulic connection left H Connection horizontal AS1 Number of connection pipes 1 connection pipe arranged 123 Diameter of the connection pipes 123 mm 2E Model with two end pieces To prevent deposits and corrosion the quality of the water for filling the registers must c...

Page 6: ...c Install the unit at a site that has good air quality Make sure that wall and ceiling correspond to the weight of the device and also allow correct mounting of the fastening elements in the ceiling The installation site must have sufficient space and the nec essary resources for carrying out mounting and mainte nance activities of all device components Make sure that the valves are easily accessi...

Page 7: ...g temperatures be low zero degrees glycol must be admixed to the coolant in a suitable ratio to ensure that the freezing point of this liquid al ways stays below the minimum temperature of the operating site Please note that the use of an antifreeze necessarily results in a loss in performance of the register Connecting the air ducts The air ducts are attached by using pipe clamps fixing lugs or t...

Page 8: ... tors etc in places with draught air or directly opposite to an air diffuser grille Temperature controls must be mounted at least 1 5 me tres above the floor Mounting temperature controls on walls toward the out doors should be avoided Prior to drilling make sure that at the location in the wall where the temperature control is attached no electric cables are present Faulty mounting of the sub ass...

Page 9: ...h allow the grille to be folded down via a rotating mecha nism on one of the profiles for safe execution of maintenance The unit is dismounted as follows DISA 300 1 H DISA 300 2 H Open the safety locks Fold the grille down and remove it This makes the grille and the registers freely accessible for cleaning purposes After completing the maintenance activity you must move the grille again to its ori...

Page 10: ...pply and hy draulic circuit must be disconnected prior to any maintenance activity If the register is dirty clean it by spraying it with water or compressed air or by evacua tion Please do not use any scouring agents for cleaning since these materials may impair or damage the DISA 300 gal vanised steel aluminium and copper and the surface coatings paints and anodised surfaces If there are larger d...

Page 11: ... values read on the meter and the following formula can be used to determine the volumetric flow V l s Primary air flow Ps Pa Static pressure The K value is taken from the following table Nozzle configuration A Nozzle configuration B NL mm Nozzle config uration 900 1200 1500 1800 2100 2400 2700 3000 A 0 42 0 62 0 79 0 99 1 16 1 32 1 51 1 69 B 0 71 1 06 1 35 1 69 1 98 2 27 2 59 2 90 C 1 32 1 96 2 5...

Page 12: ... the register Ventilation of the hydraulic system Please inform the installer Installed unfavourable or malfunctions at the temperature control or sensor Install thermostat in a different place Clogging in the interior of the unit or at the air inlet Remove foreign material and clean the inte rior of the unit The unit is losing water Condensate in the register Modify the register water inlet tempe...