Fire damper BSK-RPR 

 

 

Additional operating instructions according to ATEX 2014/34/EU

 

 

Description

 

Construction subject to change 

 

No return possible 

Version: 2020-09-01 | Page 4 

 DESCRIPTION

 

Fire dampers, installed in ventilation ducts (air conditioning 
systems), serve for the automatic locking of fire lobbies. The 
fire damper BSK-RPR conforms to EN 15650, EN 13501-3 and 
EN  1366-2.  The  BSK-RPR  has  been  tested  according  to  EN 
1366-2 in compliance with Declaration of Performance No. 
DoP-BSK-RPR-2020-09-01.  Its  classification  according  to  EN 
13501-3 is EI 30 (v

e

 i↔o) S to EI 90 (v

e

, h

o

 i↔o) S. 

According to Directive 2014/34/EU, EC Certificate of Conform-
ity Number EPS 09 ATEX 2 153 X, its use in areas subject to 
explosion hazards is permitted, not only with spring return ac-
tuator  ExMax-5.10-BF  (X14/X15),  including  safety  tempera-
ture limiter (ExPro-TT), but also with mechanical release via 
fusible  link  (manual  actuation  with  or  without  ATEX  limit 
switch ES-Ex). The fire damper is marked as follows according 
to ATEX: 

 

II 2 G Ex h IIC T6 Gb 

EPS 09 ATEX 2 153 X 

II 2 D Ex h IIIC T80°C Db 

 

The  national  standards  and  guidelines  must  be  observed  in 
connection with these additional operating instructions. 
For functional test, service, retrofitting, etc., inspection open-
ings  must  be  provided  on  site  in  suspended  ceilings,  shaft 
walls,  connected  ventilation  ducts  etc.,  if  necessary.  They 
must be built in in sufficient numbers and sizes and must not 
impair the functioning of the fire dampers.  
The fire dampers must be connected to the ventilation system 
by means of ventilation ducts either on one or on both sides. 
When  connected  on  one  side,  security  grille  made  of  non-
flammable building materials (EN13501-1) must be provided 
on the opposite side. The fire dampers can be connected to 
non-flammable and flammable ventilation ducts as well as to 
flexible spigots. 
 

 
 
The fire damper complies with the regulations of the ATEX di-
rectives and may be used in supply and return air installations 
of ventilation systems in areas subject to explosion hazards. 
 
The fire damper is certified for device group II, Zones 1, 2 and 
21, 22. 
Zones  1  and  2  represent  the  application  range  containing 
gases/vapours, while Zones 21 and 22 represent the applica-
tion range containing dusts. 
 
Classification by zone must be established by the system op-
erator or planner in compliance with current standards. 
 

Note: 

In explosion-protected zones, only devices that have an ATEX 
approval for this use may be used. It rests with the operator 
to ensure that the products are only used in zones specified 
by the product marking. 
 

SPECIAL CONDITIONS  

The attached and installed electrical devices must have a suit-
able explosion-proof design. 
It  must  be  ensured  that  all  metal  components  are  properly 
and permanently connected to the ground potential. 
 

TYPE OF IGNITION PROTECTION 

The type of ignition protection of the fire dampers is guaran-
teed by their safe design. 
 

 

QUALITY ASSURANCE 

The SCHAKO production facilities are certified according to 
the QM procedure EN ISO 9001. 
To ensure that the defined product features are adhered to 
during the production, a factory production control is carried 
out at regular intervals. In addition, a notified body carries 
out an external audit once a year. 

Summary of Contents for BSK-RPR

Page 1: ...RPR 2020 09 01 CLASSIFICATION AND STANDARDS Classification according to EN 13501 3 depending on the mounting situation EI 90 ve ho i o S Product standard EN 15650 Test standard EN 1366 2 PERFORMANCE D...

Page 2: ...Contents Construction subject to change No return possible Version 2020 09 01 Page 2 TABLE OF CONTENTS Table of Contents 2 General conditions 3 Description 4 Models and dimensions 5 Type plate 11 Ord...

Page 3: ...d DESIGNATED USE The devices have been designed for use in ventilation systems in areas subject to explosion hazards according to the ATEX marking Device group II Zones 1 2 and 21 22 These devices are...

Page 4: ...ilation system by means of ventilation ducts either on one or on both sides When connected on one side security grille made of non flammable building materials EN13501 1 must be provided on the opposi...

Page 5: ...amper blade 3 Hand lever 4 Locking profile 5 Release device 6 Fusible link 7 Mounting frame AR 8 Actuator unit 9 Earthing connection 10 Actuator ExMax 5 10 BF X14 X15 11 Safety temperature limiter Rub...

Page 6: ...le Version 2020 09 01 Page 6 BSK RPR S with mounting frame AR Figure 4 Dimensions of the BSK RPR S with mounting frame AR Figure 5 Dimensions of BSK RPR S with installation frame AR with actuator ExMa...

Page 7: ...5 58 13 40 7 03 14 85 280 278 6 31 16 55 7 79 18 03 7 17 17 41 8 65 18 89 315 313 7 14 18 40 8 62 19 88 8 13 19 39 9 61 20 87 355 353 8 08 20 53 9 56 22 01 9 19 21 64 10 67 23 12 400 398 9 09 22 89 1...

Page 8: ...ula tions Technical data actuator ExMax 5 10 BF X14 X15 Power supply 24 240 V AC DC 10 each self adaptable Frequency 50 60 Hz 20 Power consumption Holding max 20 W Heating capacity approx 16 W Current...

Page 9: ...t be necessary e g for large wall and ceiling thicknesses When connecting duct components a fastening type must be selected that causes no damage to the fire damper or its accessories During mounting...

Page 10: ...by contact or inhaling hazardous substances must be excluded by taking appropriate safety measures Prior to functional check or inspection all system components up and downstream of the device must be...

Page 11: ...damper BSK RPR Additional operating instructions according to ATEX 2014 34 EU Type plate Construction subject to change No return possible Version 2020 09 01 Page 11 TYPE PLATE Figure 10 BSK RPR type...

Page 12: ...02 MODEL S Plug in connection F Flanged connection 03 NOMINAL SIZE 100 125 140 160 180 200 224 250 280 315 355 400 450 500 in mm always three digits 04 LENGTH 580 or 455 S model 500 or 375 F model in...

Page 13: ...ess 120 mm metal post includes R04 I R22 Installation kit type GDL for wall thickness 125 mm metal post includes R04 I R23 Installation kit type GDL for wall thickness 140 mm metal post includes R04 I...

Page 14: ...amper BSK RPR Additional operating instructions according to ATEX 2014 34 EU Certificate of conformity Construction subject to change No return possible Version 2020 09 01 Page 14 CERTIFICATE OF CONFO...

Page 15: ...Fire damper BSK RPR Additional operating instructions according to ATEX 2014 34 EU Certificate of conformity Construction subject to change No return possible Version 2020 09 01 Page 15...

Page 16: ...43 Luxembourg L 2343 Luxembourg A 1060 Wien PL 05 500 Piaseczno Phone 352 403 157 1 Phone 352 403 157 1 Phone 43 1 890 24 62 Phone 48 22 7263570 Fax 352 403 157 66 Fax 352 403 157 66 Fax 43 1 890 24 6...

Page 17: ...ilippendichtung 5 Abbildung 4 Abmessungen BSK RPR S mit Anbaurahmen AR 6 Abbildung 5 Abmessungen BSK RPR S mit Anbaurahmen AR mit Antrieb ExMax 5 10 BF X14 X15 6 Abbildung 6 Abmessungen BSK RPR F 6 Ab...

Reviews: