Fire damper BSK-RPR-EU
Technical documentation
Technical data
Construction subject to change
No return possible
Version: 2021-07-01 | Page 11
Pressure loss and radiated noise
Nominal sizes 100 to
≤
250
Nominal sizes > 250 to 500
Diagram 3: Pressure loss and radiated noise
Application limits:
max. operating pressure of 1000 Pa at v
face
≤
10 m/s.
Free cross-section [m²]
Nominal
size
ØD [mm]
Free cross-section
[m²]
100
98
0.0046
125
123
0.0081
140
138
0.0107
160
158
0.0147
180
178
0.0193
200
198
0.0246
224
222
0.0317
250
248
0.0404
280
278
0.0492
315
313
0.0641
355
353
0.0836
400
398
0.1086
450
448
0.1401
500
498
0.1755
Table 6: Free cross-section [m²]
Weight table [kg]
No-
minal
size
Ø
D
[mm]
Manual release
BSK-RPR-EU-S
BSK-RPR-EU-F
L=455
L=580
L=375
L=500
100
98
2.44
2.74
2.49
2.80
125
123
2.83
3.21
2.89
3.29
140
138
3.06
3.49
3.13
3.57
160
158
3.35
3.84
3.43
3.93
180
178
3.65
4.20
3.74
4.31
200
198
3.97
4.59
4.07
4.70
224
222
4.37
5.07
4.48
5.19
250
248
4.80
5.58
4.93
5.71
280
278
6.31
7.17
6.45
7.33
315
313
7.14
8.13
7.30
8.29
355
353
8.08
9.19
8.26
9.37
400
398
9.09
10.34
9.29
10.55
450
448
10.50
11.91
10.73
12.14
500
498
11.85
13.42
12.10
13.67
No-
minal
size
Ø
D
[mm]
Spring return actuator
BSK-RPR-EU-S
BSK-RPR-EU-F
L=455
L=580
L=375
L=500
100
98
3.89
4.19
3.94
4.25
125
123
4.28
4.66
4.34
4.74
140
138
4.51
4.94
4.58
5.02
160
158
4.80
5.29
4.88
5.38
180
178
5.10
5.65
5.19
5.76
200
198
5.42
6.04
5.52
6.15
224
222
5.82
6.52
5.93
6.64
250
248
6.25
7.03
6.38
7.16
280
278
7.79
8.65
7.93
8.81
315
313
8.62
9.61
8.78
9.77
355
353
9.56
10.67
9.74
10.85
400
398
10.57
11.82
10.77
12.03
450
448
11.98
13.39
12.21
13.62
500
498
13.33
14.90
13.58
15.15
Table 7: Weight table [kg]
All data given are approximate