3.6.2 Trap disconnect jumper terminals
Cable cross section recommended for connection to the trap disconnect jumper terminals (only for
configuration with this option):
Table 21 recommended and maximum cable cross section for the trap disconnect jumper terminals
Filter
Minimum recom-
mended cable
cross section
[mm
2
]
Maximum cable
cross section
[mm
2
]
Minimum recom-
mended cable
cross section
USCS
Maximum cable
cross section
USCS
FN3470-250-99
FN3471-250-99
FN3480-315-99
FN3481-315-99
FN3482-350-99
FN3482-400-99
FN3482-450-99
FN3483-350-99
FN3483-400-99
FN3483-450-99
50
240
AWG 1/0 (0)
500kcmil
FN3470-315-99
FN3470-355-99
FN3471-315-99
FN3471-355-99
FN3480-355-99
FN3480-400-99
FN3481-355-99
FN3481-400-99
FN3482-500-99
FN3482-600-99
FN3483-500-99
FN3483-600-99
70
240
AWG 3/0 (000)
500kcmil
FN3470-400-99
FN3470-500-99
FN3471-400-99
FN3471-500-99
FN3480-500-99
FN3480-560-99
FN3481-500-99
FN3481-560-99
95
240
AWG 4/0 (0000)
500kcmil
Stripped length 29.5±0.5mm / 1.16±0.02in with ring cable lugs crimped
3.6.3 Auxiliary terminals
Recommended cable cross section for connection to the AS-AS’ and TS-TS’ auxiliary terminal:
From 0.5mm2 / AWG 20 up to 4mm2 / AWG 12
Stripped length 10.5±0.5mm / 0.41±0.02in