AIR FLOW 

It is preferable that the airflow to the power supply is filtered and below 55°C. An airflow 
resistivity (pressure drop) of below 20 kPa is required to comply with EN60950 pollution category 
II. Diffused thermal energy is required to be exhausted and replaced by air as detailed above. 
Thermal management is required where the air provided to a power  
supply complies with the power supply’s design parameters. The use of fans requires an 
increase in airflow to a minimum rate of 120m³/h (corresponding to 70 cfm). The airflow  
resistivity and respective pressure drop should be considered when a fan is required. 
 

DIRECTION OF AIR FLOW 

Typically, Schaefer modules and systems are cooled through air supply entering from  
below and exiting above, with the exception of models of series C/B 5100, 5200, 5300,  
5400, 6400 and 6600 whose airflow is from front to back. Custom designs also offer  

lateral cooling. Such details however, are project specific

 

CABINET 

 

 

 

 

 

 

 

 

A cabinet may be employed to enhance a module / system,. 

 

This  may  be  required  to  fulfill  the  increased  IP  /  NEMA  rating,  due  to  a  negative  effect  of  the  solution  on  the 
environment. 

 

Specifically,  with  unclean,  saturated,  corrosive  or  otherwise  aggressive  air  quality  it  may  be  required  to  employ  a 
cabinet with a combination of features such as hermetical sealing and air exchange amongst others. 

 

The enclosure must be capable of sustaining the weight of the modules, specifically if module support rails are used. 

 

Stationary cabinets should be fastened to the ground. 

 

The center of gravity must be as low as possible with portable systems. 

 

TRANSPORTATION OF MODULE 

The grips on the front of the modules are to assist in module insertion into a sub-rack, and not for supporting the weight of the 
module. 

 
WALL MOUNT / CHASSIS MOUNT 

Modules  with  a  mounting  plate  or  angle  are  designed  for  integration  into  the  host  equipment.  They  are  not  for  employment 
outside of an enclosure. 
 

MAINTENANCE

 

Check the applied voltages and screw connections at periodic intervals in order to recognize any irregularities in the performance 
of the power supply. If necessary, correct through adjustments and calibration. 
Clean the power supply at certain intervals from dirt and dust which may have accumulated. 
Record technical, operational and environmental data, that is to be used as a reference for evaluation. 
 
Due to storage conditions, the following maintenance may be necessary: 
   

a.

   A reforming procedure has to be done after 3 years of voltage-free storage under normal temperatures (+5° …+35°C) 

   

b.

  A reforming procedure has to be done after 1 year of voltage-free storage under extended temperatures  

         (-40° ...+5°C and +35° ... +85°C). 

   

Reforming procedure:

 

 

Due to increased leakage current of the internal electrolytic capacitors after voltage-free storage, the capacitors have 

 

to be reformed. For this purpose, the rated input voltage has to be applied to the terminals. 

 Leave the input voltage applied for a period of 1 hour. Subsequently, the unit is stored under no voltage conditions for 12 to 
48 hours at a temperature between 15°C and 35°C. 

 

Afterwards the capacitors are reformed and meet the specified values. 

 

STORAGE INSTRUCTIONS 

Storage temperature: -40°C ... +85°C 
We recommended the following conditions for storage: 
- Do not store the unit at a high temperature ( at higher temperatures the ageing process is increased ) or in high humidity. 
  Store the unit indoors at a temperature of +5 …+35°C and a humidity of less than 75% RH. 
- Keep the unit in the original package. 
If the units are stored below the operating temperature, then they have to be left for at least 5 hours at operating temperature 
conditions to ensure there is no condensing water present before operation. 
 
 