SBS-4815CT USER MANUAL
16
/
30
Power switch
The welcome screen
The main menu
spare modules to 4 cells, just like a normal module.
Disconnect all other modules.
Re-address the spare module to No. 3 to replace the failed one by entering the
‘Config Module Addr:’ of the 'Setup' menu. Set '003#' and press 'config'. The spare
module will become the new No. 3 module.
4.4.5.3
How to erase and reassign the assigned module
If you run out of spare modules, and one of the assigned modules fails (for example,
No. 3 module fails) you can erase No.6 and reassign to No.3 for this urgent
requirement.
a) Open the No. 6 module box; you will see a
small button on the PCB. (Yellow frame in the
picture.)
b) While holding this button down continuously,
connect it with 4 cells, just like you would a
normal module. It will power on, and then wait
10 seconds. Release the button.
c) Check 'BatteryView' in LCD, if Cells 20-24
(normally on No. 6 module) have no data, it
means No. 6 module has been reset to a No. 0
spare one.
d) Follow the procedure in '4.4.5.2 To Activate a No. 0 spare module', to edit it to
No. 3.
4.5 Starting Up and Input Operation
4.5.1
After the SBS-4815CT has been connected to the
battery system, turn on the “AC” power switch.
4.5.2
A welcome interface will appear where you can see the unit
identification. Press anywhere on the screen to go to the main menu. If 10
seconds elapse, the system will jump to the main menu automatically.
4.5.3
SBS-4815CT input way: press on the screen directly