Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units
│
Document 26
-859
E
NG07 │ 2015-06-04
3
Digital room controller units
3-28
3.2.4 Light:
2 groups via switch
Shade:
2 groups via changeover contacts up/down
Base
controller:
PCD7.L600
PCD7.L601
PCD7.L602
PCD7.L603
PCD7.L610
PCD7.L611
-
DIP switch
8
7
6
5
4
3
2
1
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
I1
Light group 1
I6
Shade group 1 down
I2
Light group 2
I7
Shade group 2 up
I5
Shade group 1 up
I8
Shade group 2 down
Switching commands are sent once only as status changes at the time of the action
and are not constantly repeated. This enables e.g. a network command to control the
light independently of the current switch setting. Where communication has been set
to "after change" in the associated Room F-Box for the Saia PCD
®
, the next switching
command determines the current status. If, on the other hand, communication to the
Room F-Box is set to "permanent", a different switching command applies for just a
short time until the next communication cycle.
For a combination of light control via contacts and network, it is advisable to use
electronic sensors instead of switches. See application "2 light groups with key
commands 'on' and 'off'"