Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
6-11
I/O modules PCD3
Digital input modules
6
6.2
Digital input modules
PCD3.E110
8 inputs 8 ms, 24 V
DC
PCD3.E111
8 inputs 0.2 ms, 24 V
DC
PCD3.E112
8 inputs 9 ms, 12 V
DC
PCD3.E116
8 inputs 0.2 ms, 5 V
DC
PCD3.E160
16 inputs 8 ms,
connection via 34-pole ribbon connector
PCD3.E161
16 inputs 0.2 ms,
connection via 34-pole ribbon connector
PCD3.E165
16 inputs 8 ms,
connection via 24-pole spring terminal block
PCD3.E166
16 inputs 0.2 ms,
connection via 24-pole spring terminal block
Definition of input signals
for 5 V
DC
for 12 V
DC
for 24 V
DC
PCD3.E116
PCD3.E112
PCD3.E110, PCD3.E111,
PCD3.E160
…
E166
7 V
DC
5 V
DC
2.5 V
DC
0 V
DC
1 V
DC
-7 V
DC
1
0
15 V
DC
12 V
DC
7.5 V
DC
0 V
DC
2.5 V
DC
-15 V
DC
1
0
30 V
DC
24 V
DC
15 V
DC
0 V
DC
5 V
DC
-30 V
DC
1
0
I/O modules and I/O terminal blocks may only be plugged in and removed when the