Hardware Manual PCD1.M0160E0 │ Document 27-622
|
Version ENG04 │ 2018-08-20
Saia-Burgess Controls AG
Requirement / General Information
Configuration (Device Configurator)
6-1
6
6
Configuration
(Saia PG5
®
Device Configurator / Device Configuration)
6.1 Requirements
The following description assumes that the user is familiar with the Saia PG5
®
software. If this is not the case, we recommend reading the Manual 26-733 “PG5,
software requirements, PG5 V 2.1” (or later).
6.2
General Information
This chapter describes how the Saia PG5
®
Device Configurator is used. The
Device Configurator defines:
- cyclical media mapping in order to enable a link between peripheral I/O module
values and the device resources (e.g. PCD flags and registers).
- direct access to programming instructions, for reading values from
and transmitting values to the peripheral input module.
For the PCD1.M0_, I/O handling is always enabled via direct access. There is no
“bit” access instruction: the minimum access range is “byte”. You are therefore ad-
vised to use media mapping to read and write all I/O channels. For further details,
see the online help of the Device Configurator