Savoie 174 08 02 Technical Manual Download Page 10

3.7.

Trouble shooting

Situation

Probable causes

-

Corrective action

Flames extinguish during

lighting.

¤ Very cold chimney. No draught
established.

-

Leave door ajar until fire has caught. Check air supply

in the room (page 4).

Fire extinguishes once

firestarter has burnt off.

¤ Fuel tank is empty.

-

Fill tank.

¤ Fuel valve is closed.

-

Open valve.

¤ Main regulator float not
engaging.

-

De-press the safety lever.

¤ Control knob is set on “0"

-

Adjust control knob to “1" (minimum speed).

Fire extinguishes during use.

¤ Fuel tank is empty.

-

Fill tank.

¤ Insufficient fuel.

-

Check that the de-scaler, the float regulator filter and

burner pot are cleaned.

Flame is excessively large,

smoky and sooty.

¤ Insufficient draught.

þ

-

Call your installer.

¤ Fuel adjustment made too
quickly.

-

Return control knob to minimum speed “1" ; wait for

normal combustion. (catalyser should glow red) ; wait 5

to 15 minutes between each adjustment.

Stove extinguishes and

re-lights itself.

¤ Insufficient fuel.

-

Check that the de-scaler, the float regulator filter and

burner pot are cleaned.

Stove burns noisily.

¤ Burner contains excess fuel.

-

Adjust control knob to minimum speed “1". If problem

persists call your installer.

Fire smokes. Soot build up

noticed. Flame imbalance

¤ Insufficient air supply.

-

Increase fresh air supply (open door, window ; add

make up air supply).

¤ Downdraught or blockage in
chimney.

þ

-

Check chimney for soot build up. Clean if necessary.

Ensure chimney height is sufficient and cap is not

affected by any nearby obstructions. If problem

persists call your installer.

-

Room is in negative pressure. Increase fresh air supply

(page 4).

¤ Oil flow is too low on minimum
speed setting.

þ

-

Adjust low flow rate while control is set on “1", call your

installer.

¤ Stove is not level. Flame
imbalance.

þ

-

Check level. Adjust if necessary.

¤ Catalyser not centered.

-

Center catalyser assembly

¤ The draught regulator is
blocked in open position.

þ

-

Unlock the draught regulator. Check the draught

regulator [adjustment and refit, if necessary].

Coke build up noticed.

¤ Insufficient fuel.

þ

-

Check level. Check that the de-scaler, the float

regulator filter and burner pot are cleaned.

¤ Excessive draught

þ

-

Check draught. If always excessive, a draught

stabilizer (barometric damper) must be installed to the

connector pipe.

10

Technical manual “1038”

“Savoy” - ref. 174 08 02

Instructions for user

þ

: This sign means that you should

asked for a qualified engineer to do the

work.

Summary of Contents for 174 08 02

Page 1: ...h the capital of 10 000 000 Head Office Address 2 rue Saint Gilles 68230 TURCKHEIM RCS Colmar SIREN 444 881 953 Address Administration and manufacturing BP 73 59660 MERVILLE FRANCE Telephone 00 333 28...

Page 2: ...ing the burner p 8 Instructions for user p 8 Fuel p 8 Lighting procedure p 8 Operating procedure p 9 Shutting down p 9 Recommendations p 9 Maintenance of the stove p 9 Trouble shooting p 10 Spare part...

Page 3: ...3 Optional equipment Visioflamme mirrors Glow plug ignitor Ceramic coals 1 4 Specifications Model 174 08 02 Nominal Heat Output kW 8 at maximum speed liter hr 0 95 at minimum speed liter hr 0 25 Chimn...

Page 4: ...be carried out according to local building regulations The manufacturers responsibility shall be limited to the supply of the equipment A remote acting fire valve must be fitted on the oil supply line...

Page 5: ...ector The appliance must be as close as possible to the chimney The connector pipe must be approved for installation with combustion products either 24 ga Black painted or blued steel or 316 grade 20...

Page 6: ...ses before readjusting the settings Chimney draught Fresh air inlet Oil supply Minimum speed 3 fig 9 Set the regulating knob on minimum speed 3 and let the burner run for a few minutes The flame must...

Page 7: ...with the barometric damper located at the back of the stove 1 fig 9 2 12 Maintenance of the Chimney Chimney condition should be checked at least once per year If the appliance is regularly used the ch...

Page 8: ...into the float regulator Open the front door and remove the catalyser from burner 2 fig 3 p 4 Make sure the inside of the pot is clean thoroughly and there is no oil accumulation Place 2 tablespoons o...

Page 9: ...in rotating 360 degrees two or three times CAUTION The rod is HOT Every 3 or 4 months Clean the burner completely Remove and brush off the parts of the catalyser using a soft bristle brush Loosen any...

Page 10: ...knob to minimum speed 1 If problem persists call your installer Fire smokes Soot build up noticed Flame imbalance Insufficient air supply Increase fresh air supply open door window add make up air su...

Page 11: ...26 236511 60 Burner support 01 27 239723 60 Regulator support 01 28 259015 Fixing plate 04 29 260585 Heat shield 01 30 261817 Heat shield 01 31 262220 60 Shield 01 32 262609 Heat shield 01 33 276230...

Page 12: ...12 Technical manual 1038 Savoy ref 174 08 02 Spare parts Figure 16 Spare parts view 64 65 66...

Page 13: ...Technical manual 1038 13 Savoy ref 174 08 02 Notes...

Page 14: ...our technical documents and our installation adjustment instructions 3 The installation use and maintenance of the device carried out in conformity with the applicable standards and legislation and wi...

Reviews: