Item

Environment Specification

Ground

The third kind of grounding(Connecting to the ground of high voltage
system is prohibited)

Operating environment

Avoid dust, moisture, corrosion, electric shock and external shocks

7. Digital Input (DI) Specification

Item

Digital Input (DI)

Input Signal

No voltage contact or NPN/PNP

Action driving

ON>3.5mA

OFF<1.5mA

Input Impedance

Input Impedance≈4.3KΩ

Maximum Input Current

10mA

Reaction Time

6.4ms DEFAULT, can be configured to 0.8~51.2ms

Insulation Type

Optoelectronic isolation for each channel

Input Indication

LED's lighting indicates ON, no light indicates OFF

Power supply

MPU internal power supply:DC power supply (SINK or SOURCE)
5.3mA@24VDC

8. Digital Output (DO) Specification

Item

Output point type : Relay - R

transistor output T

Maximum

load

Resistive Load

2A/1 point, 8A/4 points COM

0.5A/1 point, 2A/4 points COM

Inductive Load

50VA

5W/DC24V

Lamp load

100W

12W/DC24V

Minimum Load

10mA

2mA

Voltage Specification

Below 250VAC, 30VDC

30VDC

Drive Capability

Maximum contact capacity:
5A/250VAC

1A MAX, 10 seconds

Reaction Time

Off→On 10ms, On→off 5ms

Off→On 10μs

On→Off 120μs

Insulation Type

Mechanical isolation

Optoelectronic isolation for each
channel

Output Indication

LED's lighting indicates ON, no light indicates OFF

Power Supply

MPU internal 24VDC power supply

9. Digital Input / Output (DI/DO) Wiring Diagram

NPN Internal power

NPN External power

Summary of Contents for H Series

Page 1: ...SAVCH Programmable Logic Controller H M series PLC MPU User Manual ...

Page 2: ...Supply Specification 5 6 Environmental Specifications for Product 5 7 Digital Input DI Specification 6 8 Digital Output DO Specification 6 9 Digital Input Output DI DO Wiring Diagram 6 10 MPU Terminal Wiring Diagram 7 11 Programming Cable Wiring 8 12 Address Setting 8 13 Power Supply Wiring 8 14 Mounting and installation 8 ...

Page 3: ...e above checkpoints are not satisfactory contact your SAVCH ELECTRIC representative for a quick resolution 2 Model description 3 Product model list dimensions Ethernet Model 24VDC Model 24VDC Dimension Figure No SMC H16MRD e 0 56A SMC H16MRD 0 53A 93 95 82mm Size A SMC H16MTD e 0 58A SMC H16MTD 0 55A SMC M16MTD e 0 58A SMC M16MTD 0 55A SMC H24MRD e 0 6A SMC H24MRD 0 57A SMC H24MTD e 0 62A SMC H24M...

Page 4: ...MC H32MR 12 5W 131 95 82mm Size B SMC H32MT e 12 7W SMC H32MT 12 1W SMC H40MR e 13 3W SMC H40MR 12 7W SMC H40MT e 14 7W SMC H40MT 14 1W SMC M40MT e 14 9W SMC M40MT 14 3W SMC H60MR e 17 1W SMC H60MR 16 5W 177 95 82mm Size C SMC H60MT e 17 8W SMC H60MT 17 2W SMC M60MT e 17 9W SMC M60MT 17 3W 4 Indicator Description PWR Power indicator green Continuous ON Power good OFF Power error RUN Running indica...

Page 5: ... Consumption 25VA MAX Instantaneous Surge 20A 1 5ms MAX 220VAC 20A 1 5ms MAX 24VDC Power Loss Time 20ms or less 220VAC 10ms or less Fuse 2A 250VAC 2A 250VAC 5V Output Voltage for CPU 5V 2 2 1 2A MAX 5V 2 2 1 2A MAX 24V Output Voltage for output and extension 24V 15 15 500mA MAX 24V 15 15 500mA MAX 24V Output Voltage for input and peripheral 24V 15 15 300mA MAX Use external 24VDC power supply Insul...

Page 6: ...cates OFF Power supply MPU internal power supply DC power supply SINK or SOURCE 5 3mA 24VDC 8 Digital Output DO Specification Item Output point type Relay R transistor output T Maximum load Resistive Load 2A 1 point 8A 4 points COM 0 5A 1 point 2A 4 points COM Inductive Load 50VA 5W DC24V Lamp load 100W 12W DC24V Minimum Load 10mA 2mA Voltage Specification Below 250VAC 30VDC 30VDC Drive Capability...

Page 7: ...PNP Internal power PNP External power AC DC Relay output DC NPN Transistor output 10 MPU Terminal Wiring Diagram ...

Page 8: ... wires of 2 5mm or above for the grounding of the MPU 14 Mounting and installation The PLC should be secured to an enclosed cabinet while mounting For heat dissipation make sure to provide a minimum clearance of 50mm between the unit and all sides of the cabinet See the figure Rail Mounting Use standard 35 mm rail Screw Mounting Each MPU or extension module has two positioning screw holes the diam...

Page 9: ...s 3 Zixin Road Jiangnan Hi Tech Industrial Park Quanzhou Fujian China Tel 0595 24678267 Fax 0595 24678203 Service Network Service Hotline 4000 6161 619 Website www savch net Qualification Received ISO9001 ISO14001 and OHSAS18001 recognition All rights reserved Subject to change without further notice Sales service contact address ...

Reviews: