INSTRUCTION

 

NRT405F902

i

Consult documentation in all cases where this symbol 

is used, in order to find out the nature of the potential 

hazards and any actions to be taken

Instruction for products with software version 

1.2. 

Read this instruction before installation and 

wiring of the product.

1

NRT405F902

Room controller for controlling fan-coil units

NRT405F902 is a room controller intended for controlling fan-coil 
heaters/coolers and actuators with 0...10 V control signal. Installation 
is directly on the wall or on an electrical connection box. The fan can 
be set to one of three speeds.
NRT405F902 has change-over function and can be used for 2-pipe or 
4-pipe systems. 
For integration into a system, NRT405F902 has communication via 

RS485 (Modbus or BACnet). The device can be configured using the 

application NRT tool (version 1.3-1-05 or later), which can be down-
loaded from the SAUTER ITALIA SPA web site (www.sauteritalia.it).

Technical data

Supply voltage 

 

230 V AC ±10 %, 50/60 Hz

Power consumption 

< 3 W

Ambient temperature 

0...50°C

Ambient humidity   

Max 90 % RH

Storage temperature  

-20...+70°C

Built-in temperature sensor  NTC type, range 0...50°C
Inputs   

 

Refer to connection illustrations and    

 

 

 

table below 

Outputs  

 

Relays for fan control, 230 V AC, 3 A 

 

 

 

AO1, AO2, 0...10 V DC 

Communication   

RS485: Modbus (using automatic detection/ 

 

 

 

switching) or BACnet

Modbus  

 

8 bits, 1 or 2 stop bits. Odd, even 

 

 

 

(FI) or no parity

Communication speed 

9600, 19200, 38400 bps (Modbus and 

 

 

 

BACnet) or 76800 bps (BACnet only)

Terminal blocks    

Lift type for a maximum cable area 2.1 mm

2

Protection class    

IP20 

Pollution degree   

Overvoltage category 

3

Material casing    

Polycarbonate, PC

Dimensions  

 

102 x 120 x 29 mm

Installation

Place the controller in a location that has a temperature representative for 

the room. A suitable location is approx. 1.6 m above floor level in a place 

with unobstructed air circulation. 
Depress the locking tab in the upper edge of the controller with a 
screwdriver. Carefully turn the screwdriver until the bottom plate and the 

electronics unit are slightly separated (see figure 1). Then 

use the cutout 

that becomes visible in the edge of the bottom plate to open the upper 

edge completely (see figure 2). Do the same thing in the lower edge of the 

controller. 

Figure 1

Figure 2

Lift the electronics unit up from the bottom plate. The bottom plate with 
terminals has a number of hole combinations. Select suitable holes and 
fasten the bottom plate on the wall or connection box, so that the arrows 
on the bottom plate point upwards. Do not tighten the screws too hard!

 Disconnection

NRT405F902 should be connected to a switch or circuit breaker in 
the building installation. This switch should be in close proximity to 
the controller and within easy reach of the operator, and should be 
marked as the disconnecting device for the equipment.
Always use the circuit breaker to disconnect the controller from the 
mains supply during maintenance of the fan-coil and actuators.

Settings

Control modes

NRT405F902 can control heating and cooling in sequence or be set 
to seasonal switching between heating and cooling (change-over, see 
below).

Change-over function

NRT405F902 has an input for change-over that automatically sets the 
output AO1 to operate with heating or cooling function. A sensor of 
type PT1000 can be connected to the input and must be mounted so 
that it senses the temperature on the supply pipe to the coil.
When the temperature exceeds 28°C, the output function is set to 
heating and when the temperature drops below 16°C, the output is 
set to cooling. As an alternative, a potential-free contact can be used. 
The input function can be set to NO/NC.
To ensure satisfactory functioning when using a sensor, the system 
must have continuous primary circuit circulation. When the change-
over function is not used, the input must be left disconnected.

Operating mode

There are four different operating modes. Switching between these 
modes is performed locally.

Comfort: 

 is shown in the display. Heating and cooling have a 

smaller neutral zone NZC. An occupancy detector can be connected 
to the DI in order to select between Comfort and Economy. Switching 
between Comfort/Economy and Off can also be done via the On/Off 
button. Comfort/Economy is selected via the parameter list.

Economy (Standby):

 “Standby” is shown in the display. The heat-

ing and cooling setpoints are freely adjustable. Factory settings: 
heating=15°C, cooling=30°C.

Off:

 The controller does not heat or cool and the fan stops (unless 

mould protection has been selected, in which case the fan will still 
run).

Window: 

   is shown in the display, the controller is off and the fan 

stops (unless mould protection has been selected, in which case the 
fan will still run). The window contact is connected to the DI and must 

be configured.

10830A

 

JAN 14

EN

Summary of Contents for NRT405F902

Page 1: ... the bottom plate The bottom plate with terminals has a number of hole combinations Select suitable holes and fasten the bottom plate on the wall or connection box so that the arrows on the bottom plate point upwards Do not tighten the screws too hard Disconnection NRT405F902 should be connected to a switch or circuit breaker in the building installation This switch should be in close proximity to...

Page 2: ...y for about 5 seconds until the Service symbol is displayed and then press the INCREASE button twice First the display will show parameter 1 Use the INCREASE and DE CREASE buttons to scroll between the parameters and press the On Off button to select the desired parameter The parameter number will then be replaced by the parameter value The value can be changed using the INCREASE and DECREASE butt...

Page 3: ... NC universal input 1 0 NO 1 NC 0 38 Not used for this model 1 39 Not used for this model 1 40 Manual Auto heating output signal 0 Off 1 Manual 2 Auto 2 41 Manual Auto cooling output signal 0 Off 1 Manual 2 Auto 2 Nº Description FS 42 Heating output signal in manual mode 0 43 Cooling output signal in manual mode 0 44 Model 45 Version Major 46 Version Minor 47 Released or beta version 48 Revision 4...

Page 4: ...ol per applicazioni versione 1 3 1 05 o successiva scaricabile dal sito Web di SAUTER ITALIA SPA www sauteritalia it Dati tecnici Tensione di alimentazione 230 V CA 10 50 60 Hz Consumo energetico 3 W Temperatura ambiente da 0 a 50 C Umidità ambiente Max 90 UR Temperatura di conservazione da 20 a 70 C Sensore di temperatura integrato Tipo NTC intervallo da 0 a 50 C Ingressi Fare riferimento alle il...

Page 5: ...nte Comfort viene visualizzato nel display Riscaldamento e raffreddamento presentano una zona neutra NZC Un rilevatore di presenza può essere collegato al DI per scegliere tra Comfort ed Economy La commutazione tra Comfort Economy e Disattivazione può essere eseguita anche tramite il pulsante On Off Comfort Economy si seleziona tramite l elenco dei parametri Economy Standby Standby viene visualizz...

Page 6: ...ale per il regolatore temperatura ambiente 10 K 9 Tempo di integrazione per regolatore temperatura ambiente 300 s 10 Non usato per questo modello 11 Timer di spegnimento per la modalità Comfort 0 min 12 Ritardo di accensione per la modalità Comfort 0 min 13 Sensore collegato a AI1 0 Sensore interno 1 Sensore ambiente esterno 0 14 Sensore collegato a UI1 0 Nessuno 1 Commutazione digitale 2 Commutaz...

Page 7: ... indirizzi alle impostazioni predefinite 1 Impostazioni di fabbrica Modbus 9600 0 64 Setpoint di base Valore regolabile da 5 a 50 C 22 C Cablaggio 10 20 30 LOGIC 40 50 POWER Figura 4 Collegamenti della piastra di fondo da 0 a 10 V da 0 a 10 V B 230 V CA Commutazione 230 V CA 230 V CA 230 V CA da 0 a 10 V Figura 5 Schema di collegamento 10 L Linea 230 V CA Alimentazione elettrica 11 Non collegato 1...

Page 8: ...ischer Erkennung Umschaltung oder BACnet MS TP Modbus 8 Bits 1 oder 2 Stoppbits Ungerade gerade WE oder keine Parität Komm geschwindigkeit 9600 19200 38400 bps Modbus und BACnet oder 76800 bps nur BACnet Klemmenblöcke Lift Typ für Kabelquerschnitte bis zu 2 1 mm2 Schutzart IP20 Verschmutzungsgrad 2 Überspannungskategorie 3 Material Gehäuse Polykarbonat PC Abmessungen 102 x 120 x 29 mm Installation...

Page 9: ...dieser Parameter auf 1 gestellt wird wird nur die erste Ventilatorstufe zur An steuerung verwendet Mit Parameter 31 kann eine Grundstufe für den Ventilator bei Auto eingestellt werden Wenn dieser Parameter auf 1 gestellt wird läuft der Ventilator in allen Betriebsmodi außer dem Abschaltbetrieb und Fenster bei aktivierter Schimmelschutzfunktion läuft der Ventilator trotzdem weiter Manuelles Einstel...

Page 10: ...ntilatorstufe in Auto 0 Folgt dem Heiz Kühlstellsignal 1 Ventilatorbetrieb mit Grundstufe 1 32 Temperaturkorrektur an AI1 0 K 33 Temperaturkorrektur interner Raumfühler 0 K 34 Max SW Erhöhung bei Anpassung Einstellbarer Wert 0 13 K Basis SW 22 C 13 K 35 Max SW Senkung bei Anpassung Einstellbarer Wert 0 17 K Basis SW 22 C 17 K 36 NO NG Digitaleingang 1 0 NO 1 NG 0 37 NO NG Universaleingang 1 0 NO 1...

Page 11: ...pour les produits ayant la version 1 2 ou plus Veuillez lire cette instruction avant de procéder à l installation et au raccordement du produit NRT405F902 FR Afin d éviter tout risque d incident ou d accident veillez à respecter les conseils de sécurité donnés dans cette notice et identifiés par ce symbole Régulateur d ambiance pour le contrôle de ventilo convecteurs NRT405F902 est un régulateur d...

Page 12: ...e et de refroidissement sont réglables indépendamment Ré glages usine consigne de chauffage 15 C et consigne de refroidisse ment 30 C Arrêt Off Le régulateur ne commande ni le chauffage ni le refroidisse ment et le ventilateur est à l arrêt sauf si la protection anti moisissure a été sélectionnée Dans ce cas le ventilateur continue de tourner Fenêtre est affiché à l écran le régulateur est en mode...

Page 13: ...ur de consigne du chauffage en mode Éco 15 C 7 Valeur de consigne du refroidissement en mode Éco 30 C 8 Bande proportionnelle du régulateur 10 K 9 Temps d intégration du régulateur 300 s 10 Sans objet pour ce modèle 11 Délai de mise à l arrêt du mode Confort 0 min 12 Délai de mise en route du mode Confort 0 min 13 Type de sonde raccordée à AI1 0 Sonde interne 1 Sonde d ambiance externe 0 14 Type d...

Page 14: ...signal de sortie refroidissement 0 44 Modèle 45 Version Majeure 46 Version Mineure 47 Version officielle ou bêta 48 Révision 49 Rétroéclairage afficheur faible luminosité 10 50 Rétroéclairage afficheur luminosité élevée 30 51 Adresse PLA 52 Adresse ELA 53 Adresse Modbus 254 54 Bit de parité pour la communication Modbus 0 Pas de parité 1 Parité impaire 2 Parité paire 2 55 Déconnexion automatique Mo...

Page 15: ... 50 Agnd Commun signaux analogiques 51 AO1 Sortie analogique 1 52 AO2 Sortie analogique 2 53 A RS485 communication A 54 B RS485 communication B Protection par fusible équivalent à la somme des courants entre DO1 DO3 Directive basse tension BT Directive compatibilité électromagnétique CEM Ce produit est conforme aux exigences des directives CEM et BT et répond aux standards EN60730 1 2000 et EN6073...

Reviews: