NRT405F901 manual
Chapter 19
BACnet signals
46
Object name
Object ID
Description
Values
Writeable
Not used in this model
Binary value, 8
No
RC_Actual_L.NRTBypass
Binary value, 9
Forces the unit into Bypass
mode. Reverts automatically
after Bypass time has elapsed
(FS=120 min)
ACTIVE/
INACTIVE
Yes
RC_Actual_L.NRTShutDown
Binary Value, 10
Forces the unit into
Shutdown mode
ACTIVE/
INACTIVE
Yes
All binary values have normal polarity
Loop
Object name
Object ID
Description
Controller
Loop, 0
The NRT controller
Multistate inputs
Object name
Object ID
Description
Values
Writeable
Not used in this model
Multistate input, 0
No
RC_Actual_X.NRTUnitState
Multistate input, 1
Current running
mode
1=Off
2=Unoccupied
3=Stand-by
4=Occupied
5=Bypass
No
RC_Actual_X.NRTControllerState
Multistate input, 2
Current control
mode
1=Off
2=Heating
3=Cooling
No
RC_Actual_X.NRTFanSpeed
Multistate input, 3
Current fan speed
1=Off
2=Fan speed 1
3=Fan speed 2
4=Fan speed 3
No