background image

RDT724 F002/F022

Fr. Sauter AG – 4016 Basel (Schweiz)

Tel. +41 61 - 695 55 55   Fax +41 61 - 695 55 10

www.sauter-controls.com

E-mail: [email protected]

6/6

P100002032 003 A

D5: Switching programme 

Note:
The requirement is that a switching programme for the 
application was enabled during commissioning.

D5.1: Parameterise the switching programme 

Press

menu and –  at the same time to go to the basic 

display in the user level.

menu

Scroll until you see 
the display to select 
the switching 
programme

,

Select the switching 
programme

These options are available:

1 = Daily timer with 2 SP

2 = Daily timer with 6 SP

3 = Weekly timer with 2 SP (

)

4 = Weekly timer  with 6 SP

11 = Same as 1 + holiday period

12 = Same as 2 + holiday period

13 = Same as 3 + holiday period

14 = Same as 4 + holiday period

step

Load the switching 
programme and show 
the function

,

Select the function

These options are available:

1 = Operation as per switching 
programme

2 = Continuous reduced mode

3 = Continuous normal mode

Press 

menu

 and 

 at the same time to go to the basic display in the 

user level.

D5.2: View and change switching programme  

Press 

menu  and  –  at the same time to go to the basic 

display in the user level.

menu

Scroll until you see 
the display to select 
the switching 
programme

step

Scroll until the 
display of the first 
switching command

,

Adjust the switching 
time

step

Accept the value and 
call up the next 
switching command

,

Adjust the switching 
time

… etc. 

To add a switching command, scroll through the switching programme 
until you see this display: 

,

Adjust the switching 
time

… etc. 

Press

menu and – at the same time to go to the basic display in the 

user level.

Notes:

 means that the installation is switched to normal mode at 

this time.

 means that the installation is switched to reduced mode at 

this time.

When entering holidays, enter the start and finish dates.

 Heating applications: 

0600 hours until 2200 hours - normal mode; 2200 hours 
until 0600 hours - reduced mode.

 Ventilation applications:

0800 hours to 1800 hours - normal mode;
1800 hours to 0800 hours - reduced mode

To delete switching commands, enter commands for normal 
and reduced modes at the same time.

Setpoint     20.0°C
Act. val.    17.3°C

D400:Clk chan. 1 
 

O: Not used 

D400:Clk chan. 1 
 

3:Week 2SP 

D401:Clk C1 mode 
 

1:Auto 

Setpoint     20.0°C
Act. val.    17.3°C

D400:Clk chan. 1 
 

3:Week 2SP 

D411:Clk C1 mo 
 

06:00 

D411:Clk C1 mo 
 

07:15 

D412:Clk C1

4

mo

22:00 

D413:Clk C1

5

mo

--:-- 

Summary of Contents for flexotron 700

Page 1: ... Installation Instructions enclosed with it please read these instructions on operating it A2 Key SP Switching point abcd Key labelled abcd Factory settings Basic display showing room setpoint and actual room value B Displays and Operating Controls B1 Front view B2 Operating controls menu Load and confirm or save settings Scroll in steps of 100 step Scroll single steps Change values or settings Pr...

Page 2: ... display C2 Set the time and date continued Change the year step Accept the value and select summertime changeover display Change the changeover time step Accept the value and select wintertime changeover display Change the changeover time step Accept the value Press menu and at the same time to return to the basic display in the user level C3 Select and parameterise the application Press menu and...

Page 3: ... manual operating level is 101 C5 Manual operation continued menu The password is accepted The first analogue output is shown Change the value step The next analogue output is shown etc Unlock Lock the output 0 Unlock after exiting manual mode the output is regulated according to the control again 1 Lock the output still remains at this value after you exit from manual mode step Release fix next o...

Page 4: ...y step Display next error that has occurred step etc C8 Error messages continued After the last listed error message you see this display Use menu to delete all previous error entries Use step to go to the next display without deleting the error entries Press menu and at the same time to return to the basic display in the user level C9 Technical data Dimensions W x H x D 160 x 90 x 58 mm Weight ap...

Page 5: ...o go to the basic display in the user level 2 x menu Show measured value for first assigned analogue input step etc Show measured value for next assigned analogue input step Show value for first assigned analogue output step Show measured value for next assigned analogue output etc step Show status of assigned digital inputs contact open contact closed step Show status of first assigned relay outp...

Page 6: ...ess menu and at the same time to go to the basic display in the user level menu Scroll until you see the display to select the switching programme step Scroll until the display of the first switching command Adjust the switching time step Accept the value and call up the next switching command Adjust the switching time etc To add a switching command scroll through the switching programme until you...