circuits open or in short-circuit. Check :

Sensor resistance 
(12500 

at 20 °C, 1750 

at 70 °C)

Disconnect the sensor from the pipe: 
if the boiler starts, then the NTC 
is in contact with the earth: change 
the sensor.

NTC possibly wet: dry it

➥ 

Sensor in short-circuit 
or sensor insulation fault.

Check the electrical connections

➥ 

Interface possibly wet. Dry it or replace it.

Poor connection to the card

This fault may be occasional :

Switch OFF the boiler. Wait for 5 s 
or so and try to turn it ON.

If the fault persists, 
change the main circuit board.

➥ 

Hot water NTC disconnected

3-way valve seized 
in heating configuration when the boiler 
is set on domestic water

Pump failed

Low heating flow rate (radiators closed)

Motor connection or motor failure

➥ 

Check the safety electric valve

➥ 

Minimum ignition voltage = 175V

This fault may be occasional 
and transient

Otherwise, check the card.

➥ 

Check the position of CTN2

➥ 

Perform water topping-up

➥ 

Check the expansion vessel, 
the filling cock (may be open), 
the pressure sensore, 
the capacity of water of the installation.

Code

Fault type

Display

Checks to be performed

06

08

09

11 or 12

13

14

15

16

17

18 or 20

19

21

22

Heating sensor loop (NTC 2)

Microfast sensor loop (NTC 3).
note : a mini-accumulator NTC
fault will not lock the boiler.

Pressure sensor loop (Cp)

User’s interface

Main card

Temperature limiter 
(ensured by heating 
feed NTC: (CTN2)

Step-motor failure

Gas leak through the safety
electric valves

Network voltage too low

Communication fault

CTN2 not at the right place

Lack of water in primary circuit

Too much water pressure

Summary of Contents for ThemaClassicPlus F 24 E

Page 1: ...MEMO...

Page 2: ...le AL 13 By pass 14 Gas mechanism EV 15 Loss of water sensor Cp 16 DHW heat exchanger 17 Three way valve V3V 18 Domestic water flow sensor Db 19 Domestic water filter 20 Filling system 21 Heating safe...

Page 3: ...t 1 2 3 4 TRA CTN 4 J15 J11 3 4 2 1 1 4 5 2 3 2 0bar 45 C 1 3 5 8 7 6 1 2 3 4 5 6 7 8 9 10 11 12 13 b S1 2 1 SW 230V control board connected to 230V control board M A On Off switch P Pump V3V 3 way va...

Page 4: ...97 Maximum burner pressure mbar 29 8 32 5 Gas pressure for factory setting mbar 12 3 8 5 Minimum burner pressure mbar 5 7 4 7 Number of injectors 14 17 Hot water characteristics F 24 E F 30 E Maximum...

Page 5: ...h code 96 The following data are in read only mode If another code is entered the display goes directly to the fault log line 31 but without numbered data To access the data menu Press the mode button...

Page 6: ...reading only 13 Not used 0 to 100 C 14 Not used 0 to 100 C 15 Measured hot water storage temperature C 0 to 100 C reading only 16 Measured domestic water flow rate L mn x 10 0 to 19 9 reading only 17...

Page 7: ...is given on page 4 e g 2 16 mbar for a C 24 E with natural gas To make this setting lock the boiler at reduced pressure by setting point 8 to 1 The factory set value is noted on a label stuck on the e...

Page 8: ...g point 4 on the installer menu This value depends on the type of heating under floor heating radiators etc The slope of the probe 16 slopes are available point 6 on the installer menu To know which s...

Page 9: ...s interface or distant control panel fault 13 Main circuit fault 14 Heating feed temperature maximum limit overstepped or CTN2 out of function 15 Step motor fault gas mechanism 16 Gas safety valve fai...

Page 10: ...after 7 s check the ionizing electrode and or its proper connection verify the configuration code 23 in boiler data menu Make sure that more than 40 V are present between phase and earth Otherwise ad...

Page 11: ...ow rate radiators closed Motor connection or motor failure Check the safety electric valve Minimum ignition voltage 175V This fault may be occasional and transient Otherwise check the card Check the p...

Page 12: ...water sensor Cp S57205 Heating DHW thermistor NTC2 CTN2 S57398 Ignition electrode S10038 Flame sense electrode S10037 Ignition module S57427 Hydraulic characteristics ThemaClassicPlus F ThemaClassicP...

Reviews: