For replacement of the following components it will
be necessary to remove boiler casing panels as des-
cribed in 

‘Routine Cleaning and Inspection’.

WARNING: 

Before commencing the replacement of

any component, isolate appliance from electrical
supply and turn off gas at service cock.

To replace domestic hot water thermostat

Locate domestic hot water thermostat phial poc-

ket in underside of storage cylinder.

Remove wire clip securing thermostat phial into

pocket.

Remove two screws from front control panel and

open panel.

Remove two leads from domestic hot water ther-

mostat.

Remove domestic hot water thermostat knob by

pulling off.

Using a suitable tool, unscrew and remove nut se-

curing thermostat to control panel.

Fit replacement control in reverse order to remo-

val.

Connect leads to terminals 1 and C. The polarity is

not important.

To replace fan

Remove fan as described in ‘

Routine Cleaning

 

and

Inspection

’.

Fit replacement fan in reverse order to removal.

Reconnect electrical lead.

To replace air pressure switch

Locate air pressure switch situated outside sealed

chamber on upper right hand side, 

see diagram 5.

Remove sealed chamber cover as described in

Routine Cleaning and Inspection

’.

Hold air pressure switch and remove two securing

screws.

Carefully pull off air sensing tubes.

Disconnect electrical leads to switch.

Fit leads to terminals of replacement switch.

Reconnect short air sensing tube to connection

marked 

H

.

Reconnect long air sensing tube to connection

marked 

L

.

Fit replacement switch to boiler in reverse order to

removal.

To replace printed circuit board (PCB)

Remove two screws from front control panel and

open panel.

Carefully pull off electrical connections to PCB.

Unscrew and disconnect two incoming mains wi-

res.

Unscrew and disconnect two mains warning light

wires.

Remove screws securing PCB to control panel and

lift out PCB.

Fit replacement PCB in reverse order to removal.

Note: 

Make sure that PCB connections are fully

pushed onto replacement PCB.

To replace central heating thermistor

Drain down heating circuit of boiler only as follows:

REPLACEMENT OF PARTS

Close isolating valves on flow and return pipes on

boiler, 

see diagram 3.

Note: 1)

 These valves are closed when levers are

     at right angles to direction of flow.

2) 

It is not necessary to drain down entire

    heating system to carry out this work.

Drain boiler by attaching a plastic tube to drain

outlet and opening drain valve knob anticlockwise,
see 

diagram 4.

Locate central heating flow thermistor on central

heating flow pipe below automatic air vent

.

Remove electrical connections from thermistor.

Unscrew and remove thermistor from flow pipe.

Fit replacement thermistor in reverse order to remo-

val.

Refit electrical connections.

Open isolating valves on flow and return connec-

tions, refill, vent and pressurise boiler.

Check for leaks.

To replace central heating temperature control

Remove two screws from front panel and open

panel

.

Carefully pull off central heating temperature con-

trol plug from PCB terminal marked A5.

Carefully pull off two leads to ‘Summer/Winter’

switch.

Remove central heating temperature adjustment

knob by pushing off with suitable tool through one of
the holes in rear of control panel, 

see diagram 6

.

Using suitable tool, unscrew and remove nut secu-

ring control to control panel.

Fit replacement control in reverse order to remo-

val.

To replace pump

Drain down the heating circuit of the boiler only,

as described previously.

Note: 

It is not necessary to drain down entire heating

system to carry out this work.

Undo two pump union nuts and pull pump

forwards.

Diagram. 6

Diagram. 5

Summary of Contents for SYLVA FF 24 E

Page 1: ...Servicing instructions THIS IS A CAT II2H3 APPLIANCE SYLVA 01773 828100 IN WARRANTY TECHNICAL HELPLINE 01773 828400...

Page 2: ...2...

Page 3: ...switch 6 Printed circuit board 6 Central heating thermistor 6 Central heating temperature control 6 Pump 6 7 Temperature gauge 7 Pressure gauge 7 3 way valve head 7 3 way valve 7 Loss of water switch...

Page 4: ...fluid The maximum domestic hot water flow rate is 12 litres minute Remove boiler casing as follows Upper front panel Remove by pulling free from the spring clips at the top and bottom Side panels Rem...

Page 5: ...only of storage cylinder preferably when cold Isolate electrical supply to boiler Close isolating valve c on cold water inlet pipe see diagram 3 Drain upper section only of storage cylinder by attach...

Page 6: ...rew and disconnect two incoming mains wi res Unscrew and disconnect two mains warning light wires Remove screws securing PCB to control panel and lift out PCB Fit replacement PCB in reverse order to r...

Page 7: ...drain down entire heating system to carry out this work Remove 3 way valve head as described previously Unscrew three nuts securing 3 way valve to pipework and lift out 3 way valve making note of the...

Page 8: ...connection on fixing jig see diagram 3 Refill storage tank and vent cylinder Check for leaks To replace anode To replace anode it is necessary to drain upper sec tion only of storage cylinder preferab...

Page 9: ...nscrew and remove screws securing expansion vessel to boiler Lift vessel out of boiler Fit replacement vessel to boiler in reverse order to removal ensuring that sealing washer is fitted to pipe conne...

Page 10: ...Cold water inlet C Heating flow D Domestic hot water flow F Gas supply 1 3 way valve 2 Loss of water switch 3 Pump 4 CVI unit 5 Gas valve 6 Ignition electrode 7 Injector manifold 8 Flame detection ele...

Page 11: ...81 m3 h 2 10 kg h 2 06 kg h Gas rate minimum 1 32 m3 h 0 98 kg h 0 97 kg h Gas reference 15 1013 mbar Burner pressures burner pressures as listed in the table below must be checked after the boiler ha...

Page 12: ...tors A7 Clock option connector BR Reset button CTN Thermistor EV1 Modulating valve EV Main gas valve EX Fan E H Summer Winter switch F1 F2 F3 Fuses FA Ignition elctrode FL Flame sense electrode IG Mai...

Page 13: ...works but the heating doesn t refer to chart No 1 If heating works correctly but the hot water doesn t refer to chart No 2 IMPORTANT Always adopt a logical step by step procedure starting at the begin...

Page 14: ...tral heat ing potentiometer Replace central heating thermistor Faulty PCB replace Are heating controls calling for heat NO NO NO NO NO YES DHW ok Replace domestic hot water thermostat Replace 3 way va...

Page 15: ...fitted and free of obstructions Check for correct fit of sealed chamber cover Is pump running at full speed Does burner remain on for less than 5 seconds Is fan running at full speed Refer to chart N...

Page 16: ...al heating safety valve 56110 12 Expansion valve 6bar 56029 13 T P relief valve 7bar 56108 14 Anode 56000 15 High limit thermostat 56012 16 Ignition flame sense electrode 56002 85890 B 07 97 CHART N 5...

Reviews: