Saunacore CTY-WS16 Instructions Manual Download Page 3

If the sauna floor is made from wood or combustible materials, use a concrete
slab with a thickness of no less than 60 mm (2.5 inches) to protect the floor.
The slab must protect directly beneath the stove and extend out beyond
the stove sides and front,  400 mm in front (16 inches) and 300 mm (12 inches)
at the sides.  The slab should be just a little higher than the floor level.

Do not place any wiring or electrical equipment near the oven.

CONTACT YOUR LOCAL FIRE INSPECTOR OR LOCAL AUTHORITIES TO
OBTAIN THE COMPLETE APPROVAL AND COMPLETE SET OF INSTALLATION
INFORMATION.

Chimney Connection:

The stove has two outlets for the chimeny, one located on the top and 
another located on the back side.  Only use one, your choice.  Which ever
is used, close the other with the cap.  The diameter of the chimney pipe 
must be 2 cm (0.75 inches) larger than the diameter of the connecting pipe.

Servicing Stove:

Accumulated soot is removed through opening for cleaning which are 
located at the top of the stove covered with caps.
Stones in the oven should be inspected minimum yearly.  Small cracked
ones should be removed and changed.  For a good draught clean the
chimney regularly.  Ash bin is cleaned before adding wood (stoking) to 
promote a good passage for air circulation.  Do not place ashes in a 
combustible container.

Wood burning sauna stoves installations must be approved before using the sauna.
As we are not aware of any specific codes or regulations which govern wood burning sauna stoves.
Before installing the wood burning sauna heater, please contact your local municipal officials or
fire department to find out if any guidelines are available

3

www.saunacore.com       (905) 857-8085

A 6" diameter single wall stove pipe, used to connect the stove to the chimney, must
be installed with the crimped end towards the stove.  This will ensure that the moisture
which condenses from the burning wood will flow back into the stove.
Each joint in the stove pipe must be secured with at least three sheet metal screws.

This heater must be connected to a chimney complying with the requirements for Type
HT chimneys in the Standard for Chimneys, Factory-Built, Residential Type  and Building
Heating Appliance UL 103.

A 4.5" to 6" pipe adapter is available as an accessory.

(refer to diagrams on page 4)