TSD-1 

 

Smoke and heat detector 

 

 

 

 

 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

Firmware version 1.00 

tsd-1_en 11/19

 

SATEL sp. z o.o. • ul. Budowlanych 66 • 80-298 Gda

ń

sk • POLAND 

tel. +48 58 320 94 00 

www.satel.eu 

Summary of Contents for TSD-1

Page 1: ...TSD 1 Smoke and heat detector Firmware version 1 00 tsd 1_en 11 19 SATEL sp z o o ul Budowlanych 66 80 298 Gdańsk POLAND tel 48 58 320 94 00 www satel eu ...

Page 2: ...hall void your rights under the warranty SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and software Current information about the changes being introduced is available on our website Please visit us at http www satel eu The declaration of conformity may be consulted at www satel eu ce The following symbols may be used in...

Page 3: ...tor The detector automatically compensates for gradual changes in the optical chamber caused by deposition of dust Heat detection The heat sensor operates according to the requirements of Class A1R EN 54 5 The temperature exceeding 54 C or a too fast temperature rise see table 1 will trigger an alarm Air temperature rise velocity Lower limit of response time Upper limit of response time 1 C min 29...

Page 4: ... flashing 3 Selecting a mounting location The detector is designed for indoor installation The detector should be installed in location close to the building apartment exit e g in the hall lobby etc Fig 1 and Fig 2 In the typical home or office applications the detector should be installed on the ceiling as close as possible to the center of the room at a distance of at least 0 5 meters from the w...

Page 5: ...ng DIP switches configure the detector see Configuring the detector 5 Screw the wires to the corresponding terminals in the enclosure base see Connecting wires 6 Replace the detector cover and turn it clockwise 7 If in the premises where the detector is installed any work is being carried out that may lead to soiling of the optical chamber put a plastic dust cover on the detector and leave it ther...

Page 6: ...out EOL resistors OFF ON with EOL resistors 2EOL ON OFF Table 3 Configuring the detector output with the DIP switches shown in Fig 5 4 2 Connecting wires The terminals located in the enclosure base are designated with numbers 1 common ground 2 and 3 alarm output 4 power input 12 V DC 5 additional terminal Shown in Figs 6 and 7 are examples of how the detector can be connected to the control panel ...

Page 7: ...ng the optical chamber It is recommended that you have the optical chamber cleaned at least once a year Cleaning the chamber is necessary when the LED indicates fouling of the chamber one flash every 30 seconds 1 Turn the cover counter clockwise Fig 8 and remove it Fig 9 2 Pull aside the mounting catches Fig 10 and remove the electronics module with the optical chamber Fig 11 ...

Page 8: ...m humidity 93 3 Enclosure dimensions ø108 x 61 mm Weight 164 g The TSD 1 smoke and heat detector conforms to the essential requirements of the EU Regulations and Directives CPR 305 2011 Regulation of the European Parliament and of the Council of 9 March 2011 laying down harmonized conditions for the marketing of construction products and repealing the Council Directive 89 106 EEC on construction p...