background image

SATEL 

MPD-300 

LED 

The LED is flashing for about 15 seconds from inserting the battery, signaling the warm-up of 
the detector. The LED is also enabled in the test mode, in which it indicates: 

  periodical transmission 

– short flash (80 milliseconds), 

  alarm 

– ON for 2 seconds, 

  motion detection system failure 

– 2 flashes every 40 seconds. 

Supervision of motion detection system 

When  the  motion  detection  system  starts  malfunctioning,  the  detector  will  report  an  alarm 
during  periodical  transmission.  The  alarm  will  keep  going  until  the  fault  is  cleared  (long 
violation). 

Battery status control 

When the battery voltage is below 2.75 V, information about low battery is sent during each 
transmission. 

Electronics board 

Do not touch the pyroelectric sensor, so as not to soil it. 

 

  CR123A lithium battery. 

  detector configuration pins. For how to configure the detector, see the figures: 

–  operating mode selection: 

jumper off 

– normal mode; 

jumper on 

– energy save mode. 

–  pet immunity option enabling / disabling: 

jumper off 

– option disabled; 

jumper on 

– option enabled. 

–  sensitivity selection: 

jumper off 

– normal sensitivity (Fig. 5); 

Summary of Contents for micra MPD-300

Page 1: ...MPD 300 Wireless passive infrared detector Firmware version 2 00 mpd 300_en 06 20 SATEL sp z o o ul Budowlanych 66 80 298 Gda sk POLAND tel 48 58 320 94 00 www satel eu...

Page 2: ...improve the quality of its products which may result in changes in their technical specifications and software Current information about the changes being introduced is available on our website Pleas...

Page 3: ...ption 2 Radio communication 2 Alarms 2 Operating modes 2 Test mode 2 LED 3 Supervision of motion detection system 3 Battery status control 3 Electronics board 3 3 Selecting a mounting location 4 4 Ins...

Page 4: ...the detector sends information about its state periodical transmission Additional radio transmissions take place as a result of alarm Alarms The detector will report alarm after detecting a motion in...

Page 5: ...an alarm during periodical transmission The alarm will keep going until the fault is cleared long violation Battery status control When the battery voltage is below 2 75 V information about low batter...

Page 6: ...ED indicator tamper switch activated by detector removal from the back tamper unit tamper switch activated by cover removal PIR sensor dual element pyrosensor scale for positioning of PIR sensor again...

Page 7: ...The used batteries must not be discarded but should be disposed of in accordance with the existing rules for environment protection 1 Remove the front cover Fig 7 2 Configure the detector using the ju...

Page 8: ...he mounting screw hole facilitates positioning of the electronics board depending on the detector installation height Fig 12 12 Close and open the tamper switch that detects the cover removal to enabl...

Page 9: ...n 55 A Maximum current consumption 58 mA Detectable speed 0 3 3 m s Warm up period 15 s Recommended installation height 2 4 m Coverage area normal sensitivity 14 m x 12 m 86 high sensitivity 16 m x 18...

Reviews: